Limitid indikator GWG - type GWD -issue 2
Part no. 15 382 57 b
3 / 12
Use in areas prone to flooding
Malfunctions caused by flooding.
Suitable for installation in areas at risk of flooding only to 10 m water height.
Provide for leak-tightness between insert and tank using gasket and sealing
material, respectively.
Upon flooding, the limit indicator must be replaced.
INAPPROPRIATE USE
All uses exceeding the concept of intended use:
•
e.g. operation with different operating media,
•
operation with inflammable operating media of cat. 1, 2 or 3 with a flash point
≤
55°C
•
outdoor use
•
changes to the product or parts of the product
•
installation in a potentially explosive area
•
installation in tanks not described in issue 1 in
table 1
•
installation in pressurised tanks
USER QUALIFICATION
Installation, start-up, maintenance and restoration of the product may only be commissioned
to such companies constituting specialised companies for this work in the meaning of § 62 of
the AwSV and additionally have knowledge in the field of fire and explosion control if this work
is performed on containers with stored liquids with a flash point ≤ 55°C. This does not apply if
the system is excluded from this obligation to be installed by a specialised company according
to national regulations. These will simply be referred to below as "specialised company".
Work on electrical parts may be carried out only by an electrician qualified according to VDE
regulations or by an electrician who is qualified according to local regulations.
The specialised company and the operator must observe, comply with and understand all of
the following instructions in this assembly and operating manual.
ASSEMBLY
Before assembly, check that the product is complete and has not suffered any damage during
transport.
ASSEMBLY are to be carried out by a company specialised
.
See USER QUALIFICATION!
The specialised company and the operator must observe, comply with and understand all of
the following instructions in this assembly and operating manual. For the system to function
as intended, it must be installed professionally in compliance with the technical rules
applicable to the planning, construction and operation of the entire system.
DETERMINING THE ADJUSTING DIMENSION X
The adjusting dimension
X
mentioned in the certificate of suitability for intended use of the
building inspectorate regarding the tank, the filling system or in this manual must be
observed.
•
Determine the battery tank system and the number of connected tanks (battery tanks).
•
Please find the adjusting dimension
X
in the tables below and take into account the specific
installation situation for limit indicators.
•
The control dimension
Y
serves for verifying whether the limit indicator has been set to the
height according to the tank.
•
Determination or calculation of the adjusting dimension
X
, possibly pursuant to the options
included
in issue 1 from table 6.