Limitid indikator GWG - type GWD -issue 2
6 / 12
Part no. 15 382 57 b
INSTALLATION TO THE TANK
Assembly insert
After having DETERMINED THE ADJUSTING DIMENSION X, the insert must be locked.
Insert G 1/2
•
Set the determined adjusting dimension
X
.
•
Clamp probe tube using the cap nut of the compression
fitting by hand or using a jaw spanner so that the probe tube
cannot be moved.
Insert G 3/4
•
Loosen the locking screw on the insert.
•
Set the determined adjusting dimension
X
.
•
Tighten the locking screw so that the probe tube cannot
be moved.
Screw-in insert G 1
•
Loosen the upper locking screw .
•
Set the determined adjusting dimension
X
.
•
Tighten the locking screw a in such a way that the probe
tube cannot be moved.
•
Screw-in the tank screw-in insert into the tank
•
Tighten the upper locking screw .
•
Connecting threads present on the tank larger than G1 can be brought to the connecting
thread G1 of the insert by using commercially available reducers. Due to the partial
increase of the fitting edge, the following is applicable:
X = a + k + k
Reducer
Tank installation plate D70 for cap nut
•
Measure the determined adjusting dimension
X
from the lower
edge of the tank panel and adjust (according to the instruction
of the respective tank manufacturer).
•
Assembly according to the attached installation instructions
Part no. 15 143 50
Insert level gauge FSA
•
Loosen the locking screw on the insert.
•
Set the determined adjusting dimension
X
.
•
Tighten the locking screw so that the probe tube cannot
be moved.
•
Observe the assembly and operating manual 15 276 51 and
table 3 on the page below.
a