6.1
Display connection
The first menu, „Connection“, shows the mains voltage present and the quality of the N and PE conductor
connection.
You can check that the finger contact LED is working properly by touching the finger contact in the
individual measurement „IEA LN - Probe“ with the probe. The LED must flash.
6.2
Single-phase connection
WARNING!!!
• If voltage L1 < 207 V, or L1 > 253 V, reliable and meaningful measurements are no longer possible!
If the message ‘PE>30V!!’ is shown, there is probably a disruption in the protective earth conductor or
there may be an external voltage at the protective earth conductor (check with the finger contact)!
See „Checking the electrical connection“ on page 13 for details of how to check the protective earth
conductor.
7
Commissioning the test device
7.1
Performing a visual inspection
• See the safety instructions in Section 1!
• Visually inspect the mains connection, test device and measurement accessories!
• Heed warnings on the test device, mains adapter cable and measurement accessories!
7.2
Supplying the test device with mains voltage
The test device is supplied via the mains connection on the top of the device.
The TG Basic 2 and TG Basic 2+ devices are automatically deactivated completely after approx. 10 min.
Important note! For the TG Basic 2+ tester:
The rechargeable batteries are fully charged after approx. 5 hours of charging.
The rechargeable batteries must be fully charged before commissioning for the first time!!!
The device can only be charged when it is switched off.
The charging process is indicated by a flashing red LED.
There is no automatic deactivation if the device is in remote mode (Test-Master app).