If the output voltage is set to 200V and 208V (see “Configuring the UPS” paragraph), the maximum power output of the UPS is
reduced with respect to its rated value, as shown in the graph below:
C
ONFIGURING THE
UPS
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Language*
Selects mimic panel language
language
English
•
English
•
Italian
•
German
•
French
•
Spanish
•
Polish
•
Russian
•
Chinese
Output voltage
Selects the rated output
voltage
(Phase - Neutral)
230V
•
220V
•
230V
•
240V
Buzzer
Selects the audible alarm
operating mode
Reduced
•
Normal
•
Reduced: does not sound due to the
momentary intervention of the bypass
Operating mode**
Selects one of five different
operating modes
ON LINE
•
ON LINE
•
ECO
•
SMART ACTIVE
•
STAND-BY OFF
Battery low **
Estimated autonomy time
remaining for “battery low”
warning
3 min.
•
1
÷
7 @1 min step
Date and time**
UPS internal watch setup
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.