C
ROSS
S
ECTION OF THE
C
ABLES
We recommend the INPUT/OUTPUT and BATTERY cables be passed under the UPS.
To determine the minimum cross section of the input and output cables, see the table below:
Cross section of cables (mm2)
*
INPUT
mains /
separate bypass (optional)
OUTPUT
BATTERY
**
(optional)
kVA
PE
L1/L2/L3
N
PE
L1/L2/L3
N
PE
+/-
N
10
10
6
10
10
6
10
4
4
4
12
10
6
10
10
6
10
6
6
6
15
16
10
16
16
10
16
6
6
6
20
25
16
25
25
16
25
10
10
10
*
The cross sections indicated in the table refer to a maximum length of 10 metres
**
The maximum length of the cables for connecting the Battery Box (optional) is 3 metres
Note:
the maximum cross section of the cables that may be inserted in the terminal board is:
•
25 mm2 for trailing cables
•
35 mm2 for rigid cables
C
ONNECTIONS
The first wire to be connected is the protective earth wire, which is to be inserted in the terminal marked
PE. During operation the UPS must be connected to the earthing system
THE INPUT NEUTRAL MUST ALWAYS BE CONNECTED
Note 1
: The protection conductor (earth cable) connection must be carried out through eyelet terminal stud M6
Note 2:
the connections to the BATTERY module must only be made if the Battery Box
(optional)
is present.
I
NTERNAL TRANSFORMERS VIEW