UPS Models
10 kVA
12 kVA
15 kVA
20 kVA
Dimensions and weight
W x D x H
440 x 850 x 1320 mm
Weight without batteries
105 Kg
110 Kg
115 Kg
120 Kg
Weight with batteries
315 Kg
320 Kg
325 Kg
330 Kg
Modes and efficiency values
Operating modes
True on line double conversion
ECO mode
Smart Active mode
Stand-by Off (Emergency)
Frequency Converter
AC/AC efficiency in on line mode
≥
93.5%
≥
94%
AC/AC efficiency in Eco mode
≥
98%
DC/AC efficiency in autonomy mode
≥
92.5%
≥
93.5%
Miscellaneous
Noise
≤
48dB(A)
≤
52dB(A)
Color
RAL 7016
Ambient temperature
(6)
0 – 40 °C
(1)
To maintain the output voltage within the range of precision indicated, it may have to be recalibrated after a long period of operation
(2)
If the mains frequency is within ± 5% of the selected value, the UPS is synchronized with the mains. If the frequency is outside the
tolerance limits or running on the battery, the frequency is the value se0.1%
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains / battery / mains @ resistive load 0% / 100% / 0%
(5)
The recharging current is regulated automatically according to the capacity of the battery installed
(6)
20 – 25 °C for maximum battery life
(7)
@ 100% load & THDv
≤
1%
Battery Box
V9N2
V9S3
V9N3
Battery
Rated voltage per branch
240 Vdc
No. batteries / V / Ah
80 / 12 / 9
120 / 12 / 7
120 / 12 / 9
Miscellaneous
Ambient temperature
(1)
0 – 40 °C
Humidity
<95% non-condensing
Protective devices
Overcurrent – Short circuit
W x D x H
400 x 815 x 1320 mm
Weight
300 Kg
390 Kg
400 Kg
(1)
20 – 25 °C for maximum battery life
Summary of Contents for GM 310 PRO
Page 39: ...MENU DISPLAY ...
Page 96: ...DISPLAY MENUS ...
Page 153: ...DISPLAY MENÜ ...
Page 210: ...MENU AFFICHEUR ...
Page 267: ...MENÚ DE PANTALLA ...