background image

 

D5094S-104 

- SIL 3 Relay Low-Volt Module for 5 A NE/ND Loads 

G.M. International ISM0460-0 

 

 

 

Technical Data 

Characteristics 

Isolation (Test Voltage): 

Output/Input 2.5 KV. 

Input: 

24 Vdc nom (20 to 28.8 Vdc) reverse polarity protected, ripple within voltage limits 

 5 Vpp. Relay coils are internally protected with suppressor diodes. 

Current consumption @ 24 V:

 40 mA. 

Power dissipation @ 24 V:

 1.0 W. 

Output: 

voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 7-11 and 8-12, close when relay energized, open in de-energized condition. 

Contact material: 

Ag Alloy (Cd free), gold plated. 

Contact rating: 

5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load), 1 A 24 Vdc, 220 mA 125 Vdc, 110 mA 250 Vdc for UL. Min.switching current 1 mA. 

Contact inrush current: 

6 A at 24 Vdc, 250 Vac. 

DC and AC Load breaking capacity:

 

Mechanical / Electrical life: 

5 * 10

6

 / 3 * 10

4

 operation, typical. 

Operate / Release time: 

30 ms / 30 ms typical. 

Frequency response: 

10 Hz maximum.

 

Compatibility: 

CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 
 

Environmental conditions: 

Operating:

 temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C. 

Max altitude:

 2000 m a.s.l. 

Storage:

 temperature limits - 45 to + 80 °C. 

Safety Description: 

ATEX:

 II 3G Ex nA nC IIC T4 Gc. 

IECEx:

 Ex nA nC IIC T4 Gc. 

UL:

 NI / I / 2 / ABCD / T4 

C-UL:

 NI / I / 2 / ABCD / T4 

non-sparking electrical equipment. 
-40 °C 

 Ta 

 70 °C. 

Approvals:  

BVS 10 ATEX E 114 X conforms to EN60079-0, EN60079-15. 
IECEx BVS 10.0072X conforms to IEC60079-0, IEC60079-15. 
UL & C-UL E222308 conforms to UL 61010-1, UL 121201 for UL 
and CAN/CSA C22.2 No. 61010-1-12, CSA C22.2 No. 213-17 for C-UL. 
TUV Certificate No. C-IS-272994-01  SIL 3 conforms to IEC61508:2010 Ed. 2. 
TÜV Certificate No. C-IS-236198-09, SIL 3  Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. 

Mounting: 

EN/IEC60715 TH 35 DIN-Rail or on customized Termination Board. 

Weight:

 about 125 g. 

Connection:

 by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm

2

 (13 AWG). 

Location:

 installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4. 

Protection class:

 IP 20. 

Dimensions: 

Width 12.5 mm, Depth 123 mm, Height 120 mm. 

General Description: 

The D5094S-104 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries. 
It provides isolation between input and output contacts. A wide compatibility towards different DCS/PLC is guaranteed: driving line pulse testing, executed by DCS/PLC, is permitted by 
a dedicated internal circuit, to prevent relay and LED flickering. 
D5094S-104 has 2+2 SPST relay contacts connected in parallel and then in series to avoid spurious trip and to increase availability (see function diagram). 
High availability SIL 3 Safety Function for NE load or F&G / ND load is available. 
Load is isolated from supply on both polarities: +/AC, -/AC. 
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2. 

 

Functional Safety Management Certification: 

G.M. International is certified by TUV to conform to IEC61508:2010  
part 1 clauses 5-6 for safety related systems up to and included SIL3. 

FSM

SIL 3

0.2

0.0

V (V)

I (A)

10

20

30

40

50

100

0.3 0.4 0.5

1

2

3

Resistive

Load

200

4

300
250

0.1

5

6

DC

resistive

AC

Resistive

Reviews: