background image

 

D5037 

- SIL 2 Switch/Proximity Detector Repeater Transistor Out 

G.M. International ISM0270-3 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5037 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5037 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5037 Terminals 

Ch1 
Ch2 

7 - 8 

9 - 10 

Ch1 
Ch2 

7 - 8 

9 - 10 

Io / Isc = 22 mA 

Ch1 
Ch2 

7 - 8 

9 - 10 

Po / Po = 56 mW 

 

Ii/ Imax 

 

Pi / Pi 

 

D5037 Terminals 

D5037 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

Co / Ca = 2.41 µF 
Co / Ca = 16.8 µF 

Co / Ca = 75 µF 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50 % of Co and Lo parameters are applicable and shall not be exceeded 

(50 % of the Co and Lo become the limits which must include the cable such that 

Ci C cable 

 50 % of Co and Li  L cable 

 50 % of Lo). 

If the cable parameters are unknown, the following value may be used: Capacitance 180pF per meter (60pF per foot), Inductance 0.60µH per meter (0.20µH per foot). 

 

Co / Ca = 66 µF 

Co / Ca = 16.8 µF 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 78.3 mH 

Lo / La = 313.4 mH 
Lo / La = 626.9 mH 

IIB (C) 
IIA (D) 

Lo / La = 1028.6 mH 

Lo / La = 313.4 mH 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 635µH/

 

Lo / Ro = 2543 µH/

 

Lo / Ro = 5087 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 8347 µH/

 

Lo / Ro = 2543 µH/

 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

IIB (C) 
IIA (D) 

IIC (A, B) 

Summary of Contents for D5037D

Page 1: ...Proximity Detector Repeater Transistor Out G M International ISM0270 3 SIL 2 Switch Proximity Detector Repeater Transistor Out DIN Rail and Termination Board Models D5037S D5037D D5037S D5037D INSTRUC...

Page 2: ...ent levels open fault 0 2 mA short fault 6 8 mA Input equivalent source 8 V 1 k typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rat...

Page 3: ...IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks...

Page 4: ...the effective group See parameters indicated in the table below D5037 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5037 Terminals D5037 Associa...

Page 5: ...24 Vdc F 3 4 Out 2 SIL 2 9 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact...

Page 6: ...Ch 2 OFF operation ON operation Field Input proximity is OFF or switch is open Field Input proximity is OFF or switch is open Out 1 transistor is de energized out is open Out 2 transistor is de energi...

Page 7: ...Transistor output Pins 1 2 for Channel 1 is normally open or transistor de energized as safe state condition for OFF operation while it is closed or transistor energized for ON operation The following...

Page 8: ...esponding section as an example Connect 24 Vdc power supply positive at terminal 5 and negative at terminal 6 For Model D5037S connect positive output of channel 1 at terminal 1 and negative output at...

Page 9: ...n fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NC 1 2 1 NO 2 Output 1 NO 2 Output NC 1 2 Position in fault condition 1 2 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Li...

Page 10: ...ction IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 1 OFF 1 O...

Page 11: ...n OFF D5037S Configuration Summary Table Channel 1 2 Line fault detection SW1 SW3 Disabled switch proximity sensor OFF OFF Enabled for SIL application proximity sensor or switch with end of line resis...

Reviews: