D5037 

- SIL 2 Switch/Proximity Detector Repeater Transistor Out 

G.M. International ISM0270-3 

Ordering Information 

 

Front Panel and Features 

 



SIL 2 according to IEC 61508:2010 Ed. 2 

for Tproof = 8 / 20 years (

10% / >10 % of total SIF) for D5037S and D5037D. 



PFDavg (1 year) 1.21 E-04, SFF 77.15 % for D5037S. 



PFDavg (1 year) 1.21 E-04, SFF 78.15 % for D5037D. 



Systematic capability SIL 3 



Input from Zone 0 (Zone 20), installation in Zone 2  



NO/NC switch/proximity Detector Input, NO/NC transistor driving mode. 



Field open and short circuit detection. 



Three port isolation, Input/Output/Supply. 



EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system. 



In-field programmability by DIP Switch. 



ATEX, IECEx, UL & C-UL, EAC-EX, UKR TR n. 898, TÜV Certifications. 



TÜV Functional Safety Certification. 



High Density, two channels per unit. 



Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without 

Power Bus, or customized Termination Boards. 



250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier. 

+ Input Ch 1 for Proximity or Voltage free Contact 

Terminal block connections 

HAZARDOUS AREA 

SAFE AREA 

- Input Ch 1 for Proximity or Voltage free Contact 

+ Input Ch 2 for Proximity or Voltage free Contact 

- Input Ch 2 for Proximity or Voltage free Contact 

7

 

8

 

9

 

10

 

+ Output Ch 1 

1

 

- Output Ch 1 

2

 

+ Output Ch 2 

3

 

- Output Ch 2 

4

 

+ Power Supply 24 Vdc 

5

 

- Power Supply 24 Vdc 

6

 

7 8 

9 10 

4 3 

6 5 

Model:     D5037 

1 channel 

2 channels 

Power Bus and DIN-Rail accessories: 
Connector JDFT049    Cover and fix MCHP196 
Terminal block male MOR017  Terminal block female MOR022 

Summary of Contents for D5037D

Page 1: ...Proximity Detector Repeater Transistor Out G M International ISM0270 3 SIL 2 Switch Proximity Detector Repeater Transistor Out DIN Rail and Termination Board Models D5037S D5037D D5037S D5037D INSTRUC...

Page 2: ...ent levels open fault 0 2 mA short fault 6 8 mA Input equivalent source 8 V 1 k typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rat...

Page 3: ...IECEx UL C UL EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification High Density two channels per unit Simplified installation using standard DIN Rail and plug in terminal blocks...

Page 4: ...the effective group See parameters indicated in the table below D5037 Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5037 Terminals D5037 Associa...

Page 5: ...24 Vdc F 3 4 Out 2 SIL 2 9 In 1 Proximity voltage free Contact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact...

Page 6: ...Ch 2 OFF operation ON operation Field Input proximity is OFF or switch is open Field Input proximity is OFF or switch is open Out 1 transistor is de energized out is open Out 2 transistor is de energi...

Page 7: ...Transistor output Pins 1 2 for Channel 1 is normally open or transistor de energized as safe state condition for OFF operation while it is closed or transistor energized for ON operation The following...

Page 8: ...esponding section as an example Connect 24 Vdc power supply positive at terminal 5 and negative at terminal 6 For Model D5037S connect positive output of channel 1 at terminal 1 and negative output at...

Page 9: ...n fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 1 ON NC 1 2 1 NO 2 Output 1 NO 2 Output NC 1 2 Position in fault condition 1 2 2 ON 2 OFF Input Input Output Input Output Input CH2 Setting Li...

Page 10: ...ction IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 1 OFF 1 O...

Page 11: ...n OFF D5037S Configuration Summary Table Channel 1 2 Line fault detection SW1 SW3 Disabled switch proximity sensor OFF OFF Enabled for SIL application proximity sensor or switch with end of line resis...

Reviews: