D5037
- SIL 2 Switch/Proximity Detector Repeater Transistor Out
G.M. International ISM0270-3
Ordering Information
Front Panel and Features
SIL 2 according to IEC 61508:2010 Ed. 2
for Tproof = 8 / 20 years (
≤
10% / >10 % of total SIF) for D5037S and D5037D.
PFDavg (1 year) 1.21 E-04, SFF 77.15 % for D5037S.
PFDavg (1 year) 1.21 E-04, SFF 78.15 % for D5037D.
Systematic capability SIL 3
Input from Zone 0 (Zone 20), installation in Zone 2
NO/NC switch/proximity Detector Input, NO/NC transistor driving mode.
Field open and short circuit detection.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
In-field programmability by DIP Switch.
ATEX, IECEx, UL & C-UL, EAC-EX, UKR TR n. 898, TÜV Certifications.
TÜV Functional Safety Certification.
High Density, two channels per unit.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without
Power Bus, or customized Termination Boards.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
+ Input Ch 1 for Proximity or Voltage free Contact
Terminal block connections
HAZARDOUS AREA
SAFE AREA
- Input Ch 1 for Proximity or Voltage free Contact
+ Input Ch 2 for Proximity or Voltage free Contact
- Input Ch 2 for Proximity or Voltage free Contact
7
8
9
10
+ Output Ch 1
1
- Output Ch 1
2
+ Output Ch 2
3
- Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
7 8
9 10
2
1
4 3
6 5
Model: D5037
1 channel
S
2 channels
D
Power Bus and DIN-Rail accessories:
Connector JDFT049 Cover and fix MCHP196
Terminal block male MOR017 Terminal block female MOR022