11
D5037
- SIL 2 Switch/Proximity Detector Repeater Transistor Out
G.M. International ISM0270-3
Line fault detection
SW1
Disabled
(switch/proximity sensor)
OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes transistor in fault condition)
ON
IN/OUT Operation
SW2
NO-NC or NC-NO
ON
NO-NO or NC-NC
(for SIL application)
OFF
D5037S Configuration Summary Table
Channel
1
2
Line fault detection
SW1
SW3
Disabled
(switch/proximity sensor)
OFF OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes transistor in fault condition)
ON ON
IN/OUT Operation
SW2
NO-NC or NC-NO
ON
NO-NO or NC-NC
(for SIL application)
OFF
Channel
1
2
SW4
ON
OFF
D5037D Configuration Summary Table
SW1 SW2 SW3 SW4
OFF OFF OFF OFF
DIP Switch factory settings (valid for D5037S and D5037D)
Configuration
Note: SW3 and SW4 not used.
Note: SW3 and SW4 used only in D5037D.