background image

 

D5031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

G.M. International ISM0107-11 

Parameters Table 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Device Parameters 

D5031 Associated 

Apparatus Parameters 

Must 

be 

Hazardous Area/ 

Hazardous Locations 

Cable Parameters 

Uo / Voc = 10.5 V 

Ui / Vmax 

In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check 
its suitability for the Hazardous Area/Hazardous Locations and group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded 
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D5031 series Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, 
check that added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the 
effective group. See parameters indicated in the table below: 

D5031 Terminals 

Ch1 
Ch2 

7 - 8 

9 - 10 

Ch1 
Ch2 

7 - 8 

9 - 10 

Io / Isc = 22 mA 

Ch1 
Ch2 

7 - 8 

9 - 10 

Po / Po = 56 mW 

 

Ii/ Imax 

 

Pi / Pi 

 

D5031 Terminals 

D5031 Associated Apparatus 

Parameters Cenelec (US) 

Ci / Ci  C cable 

 

Co / Ca = 2.4 µF 

Co / Ca = 16.8 µF 

Co / Ca = 75 µF 

For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1% of the Co and Lo parameters of the Associated Apparatus (excluding the cable), 
then 50% of Co and Lo parameters are applicable and shall not be exceeded 

(50% of the Co and Lo become the limits which must include the cable such that Ci C cable 

 

50 % of Co and Li L cable 

 50 % of Lo). The reduced capacitance of the external circuit (including cable) shall not be greater than 1 

μ

F for Groups I, IIA, IIB and 600 nF for 

Group IIC. If the cable parameters are unknown, the following value may be used: Capacitance 200 pF per meter (60 pF per foot), Inductance 1 µH per meter (0.20 µH per foot). 

 

Co / Ca = 66 µF 

Co / Ca = 16.8 µF 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Li L cable 

 

IIC (A, B) 

Lo / La = 78.3 mH 

Lo / La = 313.4 mH 
Lo / La = 626.9 mH 

IIB (C) 
IIA (D) 

Lo / La = 1028.6 mH 

Lo / La = 313.4 mH 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

Li / Ri device and 

L cable / R cable 

 

IIC (A, B) 

Lo / Ro = 635.9µH/

 

Lo / Ro = 2543.9 µH/

 

Lo / Ro = 5087.9 µH/

 

IIB (C) 
IIA (D) 

Lo / Ro = 8347.4 µH/

 

Lo / Ro = 2543.9 µH/

 

IIIC (E, F, G) 

Ch1 

Ch2 

7 - 8 

9 - 10 

IIB (C) 
IIA (D) 

IIC (A, B) 

Summary of Contents for D5031D

Page 1: ...Detector Repeater Open Collector Output G M International ISM0107 11 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D5031S D5031D D503...

Page 2: ...K typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rating 100 mA at 35 Vdc 1 5 V voltage drop Leakage current 50 A at 35 Vdc Respons...

Page 3: ...safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO CCC EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and...

Page 4: ...Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5031 Terminals D5031 Associated Apparatus Parameters Cenelec US Ci Ci device C cable Co Ca 2 4 F C...

Page 5: ...tact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5031D Duplicator...

Page 6: ...idual conductor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm The wiring cables have to be proportionate in base to the current and the length of the cabl...

Page 7: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2...

Page 8: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output...

Page 9: ...n 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity se...

Page 10: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF...