10 

D5031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

G.M. International ISM0107-11 

Line fault detection 

SW1 

Disabled 

(switch/proximity sensor) 

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

ON 

SW5 

OFF 

ON 

IN/OUT Operation 

SW2 

NO-NC or NC-NO 

ON 

NO-NO or NC-NC 

(for SIL application) 

OFF 

D5031S Configuration Summary Table 

 

WARNING:

  Dip-switch 7-8 must be set to “OFF” position. 

Channel 

Line fault detection 

SW1 

SW5 

SW3 

Disabled 

(switch/proximity sensor) 

OFF OFF OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes transistor in fault condition) 

ON ON ON 

1  

IN/OUT Operation 

SW2 

NO-NC or NC-NO 

ON 

NO-NO or NC-NC 

(for SIL application) 

OFF 

Channel 

SW4 

ON 

OFF 

Output 2 Operation 

SW6 

SW7  SW8 

Mode 

SW4 

Duplicator  

De-energized in 
fault condition 
(for SIL application) 
if line fault 
detection enabled 
(SW1 ON) 

ON 

OFF ON 

Parallel 
(for SIL 

applica-

tion) 

Set equal 

to SW2 

Not specified 
Fault condition 

OFF Reverse 

Set opposite 

to SW2 

OFF 

(for SIL application) 

ON   OFF 

NO ON 

NC 

(for SIL 

applica-

tion) 

OFF 

Fault Output  

D5031D (used as double channel) Configuration Summary Table 

 

WARNING:

 dip-switch 6-7-8 must be set to “OFF” position. 

D5031D (used as duplicator or fault output) Configuration Summary Table 

 

WARNING:

 Terminals 9-10 must be shorted to set module as Duplicator or Fault Out. Dip-switch 3 must be set to “OFF” position. 

SW1  SW2  SW3  SW4  SW5  SW6  SW7  SW8 

OFF OFF OFF OFF OFF OFF OFF OFF 

DIP Switch factory settings (valid for D5031S and D5031D)

 

Configuration 

Line fault detection 

SW1  

SW5 

Disabled 

(switch/proximity sensor)  

OFF  

OFF 

Enabled, for SIL application 

(proximity sensor or switch with end of line resistors, 

detects field open circuit and short circuit, 

de-energizes relay in fault condition) 

Output 1,  

(for SIL application) 

De-energized in Fault condition 

ON 

Output 1, 

Not specified Fault condition 

OFF 

ON  

IN/OUT Operation Output 1 

SW2 

NO-NC or NC-NO 

ON 

NO-NO or NC-NC 

(for SIL application) 

OFF 

Summary of Contents for D5031D

Page 1: ...Detector Repeater Open Collector Output G M International ISM0107 11 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D5031S D5031D D503...

Page 2: ...K typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rating 100 mA at 35 Vdc 1 5 V voltage drop Leakage current 50 A at 35 Vdc Respons...

Page 3: ...safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO CCC EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and...

Page 4: ...Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5031 Terminals D5031 Associated Apparatus Parameters Cenelec US Ci Ci device C cable Co Ca 2 4 F C...

Page 5: ...tact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5031D Duplicator...

Page 6: ...idual conductor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm The wiring cables have to be proportionate in base to the current and the length of the cabl...

Page 7: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2...

Page 8: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output...

Page 9: ...n 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity se...

Page 10: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF...

Reviews: