background image

 

D5031 

- SIL 3 Switch/Proximity Detector Repeater Open Collector Output 

G.M. International ISM0107-11 

D5031 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN/IEC60715 TH 35 DIN-Rail located in Safe Area or Zone 2, Group IIC, Temperature T4, 
Hazardous Area within the specified operating temperature limits Tamb –40 to +70 °C, and connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D5031 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules, particular care 
shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Zone 2. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. 
Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 D5031 module is a unit suitable for applications requiring SIL 3 level (according to IEC 61508) in safety related systems for high risk industries. 
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NO or NC optocoupled open collector transistor output. 
Each channel enables a Safe Area load to be controlled by a switch, or a proximity detector, located in Hazardous Area. 
Fault detection circuit (DIP switch configurable) is available for both proximity sensor and switch equipped with end of line resistors. In case of fault, when enabled it de-energizes 
the corresponding output transistor and turns the fault LED on; when disabled the corresponding output transistor repeats the input line open or closed status as configured. 
D5031D is programmable via dip switches as single input and two independent outputs. Out 2 can be programmed for output duplicating Out 1 or Fault detection Out. 
In case of duplication, transistor driving can be independently configured for each output. 
In case of fault output, transistor driving can be programmed as normally close or normally open. 
Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and connecting line are displayed by signaling LEDs 
(green for power, yellow for status and red for fault condition). 
 

Note:

 use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a R1=1 K

 typical (470 

 to 2 K

 range) 

resistor in series and a R2=10 k

 typical (5 K

 to 15 K

 range) resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of 

contact close/open and a line open/short circuit fault. 

Installation 

 D5031 series are Switch/Proximity Detector Interface housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail, with or without Power Bus or on customized 
Termination Board. 
D5031 series can be mounted with any orientation over the entire ambient temperature range. 
Electrical connection are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage 

(for Zone 2 installations check the area to be nonhazardous before servicing)

. Connect only one individual conductor per each clamping point, use conductors up to 2.5 mm² 

(13 AWG) and a torque value of 0.5

-

0.6 Nm. The wiring cables have to be proportionate in base to the current and the length of the cable. 

In case of installation in zone 2, the connecting cables of non-intrinsically safe circuits must be safely routed in a cable duct or similar. The distance between the pluggable connection 
terminal and the cable duct should not exceed 500 mm cable length. 
On the section “Function Diagram” and enclosure side a block diagram identifies all connections. 
Identify the number of channels of the specific card (e.g. D5031S is a single channel model and D5031D is a dual channel model), the function and location of each connection terminal 
using the wiring diagram on the corresponding section, as an example: 
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”. 
For Model D5031S connect positive output of channel 1 at terminal “1” and negative output at “2”. 
For Model D5031D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”. 
For Model D5031S, in case of Proximity or Voltage free Contact, connect the wires at terminal “7” for positive and “8” for negative. 
For Model D5031D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2. 
 
Intrinsically Safe conductors must be identified and segregated from non I.S. and wired in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other 
and do not produce any unintentional connection. 
Connect SPST output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc (

 1.5 V voltage drop)). 

The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The equipment shall only be used in an area of at least 
pollution degree 2, as defined in IEC 60664-1. When installed in EU Zone 2, the unit shall be installed in an enclosure that provides a minimum ingress protection of IP54 in accordance 
with IEC 60079-0. When installed in a Class I, Zone 2 Hazardous Location, the unit shall be mounted in a supplemental AEx or Ex enclosure that provides a degree of protection not less 
than IP54 in accordance with UL/CSA 60079-0. When installed in a Class I, Division 2 Hazardous Location, the unit shall be mounted in a supplemental enclosure that provides a degree 
of protection not less than IP54. The enclosure must have a door or cover accessible only by the use of a tool. The end user is responsible to ensure that the operating temperature of 
the module is not exceeded in the end use application. 
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. 
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water. 

Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5031 series must be cleaned only with a damp or antistatic cloth. 

Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized modification must be avoided. 
D5031 series must be connected to SELV or PELV supplies. 
All circuits connected to D5031 series must comply with the overvoltage category II (or better) according to EN/IEC60664-1. 

 

 

Start-up 

 Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires, also check that Intrinsically Safe conductors 
and cable trays are segregated (no direct contacts with other non I.S. conductors) and identified either by color coding, preferably blue, or by marking. Check conductors for exposed 
wires that could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance 
with condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault leds condition as well as output to be correct. 

 

Summary of Contents for D5031D

Page 1: ...Detector Repeater Open Collector Output G M International ISM0107 11 SIL 3 Switch Proximity Detector Repeater Transistor Open Collector Output DIN Rail and Termination Board Models D5031S D5031D D503...

Page 2: ...K typical 8 V no load 8 mA short circuit Output voltage free SPST optocoupled open collector transistor Open collector rating 100 mA at 35 Vdc 1 5 V voltage drop Leakage current 50 A at 35 Vdc Respons...

Page 3: ...safety system In field programmability by DIP Switch ATEX IECEx UL C UL FM FMC INMETRO CCC EAC EX UKR TR n 898 T V Certifications T V Functional Safety Certification Type Approval Certificate DNV and...

Page 4: ...Terminals Ch1 Ch2 7 8 9 10 Ch1 Ch2 7 8 9 10 Io Isc 22 mA Ch1 Ch2 7 8 9 10 Po Po 56 mW Ii Imax Pi Pi D5031 Terminals D5031 Associated Apparatus Parameters Cenelec US Ci Ci device C cable Co Ca 2 4 F C...

Page 5: ...tact In 2 Proximity voltage free Contact voltage free Contact voltage free Contact R1 R2 R1 R2 Resistors R1 R2 used with voltage free contact required for line fault detection MODEL D5031D Duplicator...

Page 6: ...idual conductor per each clamping point use conductors up to 2 5 mm 13 AWG and a torque value of 0 5 0 6 Nm The wiring cables have to be proportionate in base to the current and the length of the cabl...

Page 7: ...ity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition 7 NO 8 OR NC 7 8 7 NO 8 OR NC 7 8 1 OFF 5 OFF 1 ON 5 ON NC 1 2 1 NO 2 Output 1 NO 2...

Page 8: ...C Mode ON OFF OFF ON Disabled switch proximity sensor Enabled proximity sensor or switch with end of line resistors de energizes transistor in fault condition No Fault No Fault 1 OFF 5 OFF 5 ON Output...

Page 9: ...n 1 2 3 4 7 8 must be set to OFF position 3 4 6 Not used 5 6 7 8 ON CH Setting Line fault detection IN OUT Operation NO NC or NC NO NO NO or NC NC Disabled switch proximity sensor Enabled proximity se...

Page 10: ...n fault condition for SIL application if line fault detection enabled SW1 ON ON OFF ON Parallel for SIL applica tion Set equal to SW2 Not specified Fault condition OFF Reverse Set opposite to SW2 OFF...

Reviews: