5
D5031
- SIL 3 Switch/Proximity Detector Repeater Open Collector Output
G.M. International ISM0107-11
Function Diagram
HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC,
HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D,
CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1,
CLASS I, ZONE 0, GROUP IIC
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
Internal Dip switches programmable
MODEL D5031D
5 +
6 -
1 +
2 -
Out 1 (SIL 3)
10
=
=
=
=
7
8
Termination
board
connector
Power and
Fault Bus
Supply 24 Vdc
+
-
F
3 +
4 -
Out 2 (SIL 3)
=
=
=
=
9
+
-
In 1
Proximity
voltage free
Contact
+
-
In 2
Proximity
voltage free
Contact
voltage free
Contact
voltage free
Contact
R1
R2
R1
R2
Resistors R1 - R2 used with
voltage free contact required
for line fault detection.
MODEL D5031D Duplicator and Fault Out
5 +
6 -
1 +
2 -
Out 1 Signal (SIL 3)
=
=
=
=
7
8
Termination
board
connector
Supply 24 Vdc
Power and
Fault Bus
+
-
F
3 +
4 -
Out 2 Duplicator or Fault
9
10
+
-
In
Proximity
voltage free
Contact
voltage free
Contact
R1
R2
Resistors R1 - R2 used with
voltage free contact required
for line fault detection.
Terminals 9-10 must be
shorted to set module as
Duplicator or Fault Out
MODEL D5031S
6 -
1 +
2 -
Out (SIL 3)
=
=
=
=
7
8
Termination
board
connector
Power and
Fault Bus
Supply 24 Vdc
+
-
F
5 +
+
-
In
Proximity
voltage free
Contact
voltage free
Contact
R1
R2
Resistors R1 - R2 used with
voltage free contact required
for line fault detection.
(SIL 3)