Global Mainstream Dynamic Energy Technology Ltd.
- 41 -
User Manual
GHESS 9.8-14.4-TH hybrid system
4.1.5.14 Setting Feed-in Grid Percentage
Figure 47 Feed-in grid percentage setting
FED refers to feed-in grid percentage. The system is not allowed to feed any energy into the grid
if the FED value is set to 0%. The system is free to export to the grid if the FED setting to 100%.If the
FED is set to 10%, then the largest power allowed to be fed into the grid is 9600W*10%=960W.
The default FED value is 100%; please press “OK” to modify it.
4.1.5.15 Restore to Factory Setting
Press “
▲
”to enter setting interface as shown in Figure .
Figure 48 Restore to factory setting
RST refers to restore to the factory setting. Please input the value “1111” if you need to restore
the system into the initial setting out of factory. Press “ESC” to quit from the setting page and
enter the display menu.
Note: The setting should be operated when the Powervortex 309KTL is under “wait” status,