CONVENTIONAL SOUNDER CIRCUITS
2 individually programmed. Both circuits are currently limited and monitored for both
open and short circuit fault conditions.
10k Ohm E.O.L. resistors are used.
Maximum current rating per circuit 250mA.
AUXILIARY RELAY OUTPUTS
2 voltage free changeover relay outputs used for fire indication.
1 voltage free relay output for fault indication. Remains energized (normally closed) under
normal condition and de-energized when any fault condition appears on the system.
Maximum current rating for each relay contact 2A @ 30V DC resistive /
0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive.
GRAPHICAL LCD DISPLAY
240X64 pixels blue backlit
COMMUNICATION CHANNELS
3x configurable communication ports
BMS OUTPUT
ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring),
MODBUS RTU, ESPA 4.4.4
SOFTWARE CONNECTION
Micro USB tipo B
EVENT LOG
10,000
OPERATING TEMPERATURE
-10
º
C to +50
º
C
RELATIVE HUMIDITY
85% (non-condensing)
PROTECTION
IP30 / IP65
DIMENSIONS
273 (L) x 404 (A) x 107 (P) mm
WEIGHT
Empty - 1.6Kg / Including sealed lead acid batteries: 2 x 12V 12AH - 7.0Kg
COLOR
White (RAL9003) or Red (RAL3001)
WARNING!
In case of a short circuit or interruption of the analogue detection loop, only a
maximum of 32 detectors or call points (per loop) can be prevented, at any given time, of
transmitting a fire alarm. In order to assure compliance with EN54-2 clause 12.5.2 loop isolators have to be
installed every 32 devices in the loop.