BATTERY FAULT MESSAGE TEST
This test should be performed for each set of batteries. Test only the actual battery connections.
After a short delay, the SUPPLY FAULT
LED will be ON, the panel buzzer
sounds and the "Battery Fault" message
appears on the LCD Display.
Replace the link between the batteries and reset the
panel (SYSTEM RESET) to clear the fault indication.
POWER FAILURE TEST
Carry out this test to check that the battery system works
correctly when power fails.
Switch off the mains supply to the panel. After a short
delay, the amber SUPPLY FAULT LED will be ON and the
LCD displays the message "Primary Supply Fault". The
fault buzzer sounds.
Switch the mains supply back on and press the SYSTEM
RESET switch. The SUPPLY FAULT LED extinguishes, the
fault message is removed from the LCD and the buzzer
stops sounding.
WARNING:
It is only possible to view BATTERY FAULT MESSAGE TEST, POWER FAILURE TEST and
PROGRAMMING FUNCTIONS if the NODE+ is connected to an EXTERNAL CHAMELEON DISPLAY.
NODE+ / Installation & Commission Manual / © GFE 220331