8-4 Other Features
These are programming functions that do not fall into any other category.
8-4-1 Active/Installation Mode
An essential function. The system should always be left in ACTIVE mode, unless the system is being installed
and debugged.
When the system is set to Installation Mode the green SYSTEM ON LED on the front panel of the Panel
and Repeaters will flash.
Whilst in Installation Mode the system will automatically detect and record the presence of all connected devices.
To install the system first ensure all detectors, sounders and modules are connected and have power. Next select
Installation Mode using this function, exit programming mode and press SYSTEM RESET.
Once the system has been in Installation Mode for 90 seconds then the system can be put into Active Mode.
Note that there is no clear end to Installation mode because the system is constantly looking and learning. However if the
system is put into Active Mode and Installation Mode hasn’t had time to identify all system components, you will very
quickly be greeted with error reports regarding the presence of unexpected devices.
If devices are ever removed, replaced or added then Installation Mode must be selected so that the system can learn the
new configuration. If you do not do this, the system will report a fault.
8-4-4 Set User Access Code
This function allows the installer to change the customer Access Code. Use 1
►
2
▲
3
▼
to change the code sequence.
8-4-5 Set User Functions
Allows the user access level to be set for every programming function.
Settings are: NONE - READ ONLY - FULL ACCESS
Do not set 8-4-5 Set User Functions to FULL ACCESS or the user will be able to enable all the other functions!
It is not appropriate to set some functions to READ ONLY - for example “8-3-4 Calculate Program Flash Checksum“.
The default setting for all programming functions is NONE.
8-4-6 Select language
Allows the language setting for the system to be set.
Do this carefully, you will need to navigate back to this function to change it back again.
All text in the system will be changed to use the selected language. The change will take effect when ENTER is pressed.
8-4-8 Set Installer Access Code
This function allows changing the Installer Code without requiring knowledge of the Factory Code.
Display will show:
ENTER PRESENT CODE
ENTER NEW CODE
CONFIRM NEW CODE
8-4-9 Set Master Access Code
This function allows changing the Master Code without requiring knowledge of the Factory Code.
Display will show:
ENTER NEW CODE
CONFIRM NEW CODE
8-5 Network Configuration
All related with Network configurations and Network Protocols
8-5-1 Configure Panel Number
This function allows changing the Panel Network Number (address)
This should be unique in the network.
8-5-2 Known Panels
This function will show how many panels are being recognized on the network and all addresses detected. It will also
show its own Address on the network.
NOTE:
This function will only show the panels that are being listened to (RX). Meaning that this will only evaluate the
receiving transmission path. For further troubleshoot info, please refer to the Chameleon Communications manual.
NODE+ / Installation & Commission Manual / © GFE 220331