NOTE:
The CHAMELEON-REP has its own network address, and it is considered a Network Panel, acting as a system
repeater. It records all received network events into its own LOG.
NOTE:
The CHAMELEON DISPLAY does not have a network address. It is a simple extra display, without any network
processing capability, acting only as an extra display of the connected panel.
UI Connection
To connect a UI to a Node+ the user can connect one of the channels ( CH1, CH2 or CH3) of the UI to the “Display” channel
of the NODE+.
Chameleon Displays and Repeaters are installed in a similar manner to Control Panels.
Since the Repeaters don’t have a dedicated power supply, they can be connected to any NODE “Aux Power Supply”. Each
NODE+ panel can power a maximum of 3 CHAMELEON REP or 3 CHAMELEON DISPLAY.
NOTE:
For more detailed information on the network topologies please refer to
the “Chameleon Communications Manual”.
NODE+ / Installation & Commission Manual / © GFE 220331
17