B) In case that all modules are not responding
( all modules have communication error)
In order to find module that “blocks” communication follow instructions below:
1
. Disconnect RJ45 connector between
first
I
nput module and second
I
nput module as shown bellow.
Light failure
ITNSL detects light faiulre by monitoring current lights circuit. When current drops bellow limit it activates
alarm.
IMPORTANT!!!
Even though l
ight
failure is indicated
,
power supply can be still present on terminals.
Switch off light on main unit and check if power supply is present on light circuit.
1. Check lights fuses
2. Before replacing fuses check lights circuit for short circuit/earthning (do not connect lights if lights cables are
in short circuit or have earth fault).
3. Check light
4. Replace fuses
5.
Switch
on light
6. Visually check operation of light
In case that light is still not operating
,
light input
circuit is damaged. Connect light to free input and reconfigure
system.
CON3
CON
2
CON
1
CON
2
CON
1
TO
NEXT
UNIT
50 51
50 5150 51
50 5150 51
L
N
L
N
L
N
L
N
L
N
CON1
CON2
MAIN UNIT
ITNSL-01TP
CON1
CON2
CON3
AUDIO ALARM ACCEPT INPUT
AL
2
2 3 4
5 6 7 8 9 10
12 13 14 15 16
1
AL1
AL
3
SYS
C.O. VOLTAGE-FREE
OUTPUT CONTACT
18 19 20
17
21
SYSTEM OPERATING
COMMON ALARM OUTPUT
B A B A
-
RX
TX
NMEA 0183
RECIEVER
NMEA 0183
TRANSMITTER
CON3
INPUT
MODULES
Shown 230/115 V ac modules
Summary of Contents for NL95
Page 1: ...Rev 4 Print date 2021 05 05 NL95 Touch Screen Navigational Light Controller NL95 User manual ...
Page 2: ...Rev 4 Print date 2021 05 05 NL95 ...
Page 42: ...Rev 4 Print date 2021 05 05 38 NL95 6 2 Configuration setup form ...
Page 51: ...Rev 4 Print date 2021 05 05 47 NL95 9 2 Configuration setup form ...