o
Release
Prog
button and press briefly once again within 10 seconds.
The status LED flashes more slowly for approx. 5 seconds.
The device is reset to default setting.
6 Appendix
6.1 Technical data
Rated voltage
AC 230 V ~
Mains frequency
50 / 60 Hz
Ambient temperature
-25 ... +70 °C
Switching current at 35 °C
Ohmic
16 A (AC1)
For switching current >10A connecting cable 2.5mm²
Fluorescent lamps
4 AX
Minimum switching current AC
100 mA
Contact type
µ
Standby power
0.5 W
Connected load at 35 °C
Incandescent lamps
2300 W
HV halogen lamps
2000 W
Tronic transformers
1500 W
Inductive transformers
1000 VA
HV-LED lamps
typical 500 W
Compact fl lamp.
typical 500 W
Fluorescent lamps, uncompensated
920 VA
Capacitive load
690 VA (560 µF)
Connection
single stranded
0.75 ... 4 mm²
Finely stranded with conductor sleeve
0.75 ... 2.5 mm²
Dimensions Ø×H
53×28 mm
Radio frequency
868.0 ... 868.6 MHz
Transmission capacity
max. 20 mW
Transmitting range in free field
typ. 100 m
Receiver category
2
6.2 Parameter list
The device parameters can be changed with the eNet server:
Settings window
Device settings
Parameters
Setting options, Basic
setting
Explanations
Manual commissioning
On, Off
Basic setting: On
Disables manual
commissioning for all device
channels. In the "Off" setting,
the device cannot be reset to
the factory setting.
Repeater mode
On, Off
Basic setting: Off
In addition to its other
functions, the device can be
used as a repeater. In the
"On" setting, the device
repeats all the received
telegrams.
32581212
10499450
09.05.2016
6/11
eNet
Wireless switching/momentary-contact actuator, 1-gang Mini, Wireless
switching/momentary-contact actuator, 1-gang Mini, zero-voltage