Gira 5423 00 Operating Instructions Manual Download Page 5

i

In installation positions that are not easily accessible, turn the operating mode switch to
position 

PC

 after commissioning and performing a function test. Subsequent changes to

the device settings can thus be carried out with the aid of the eNet-Server without involving
excessive installation work.

o

Mount the cover.

5.2 Commissioning

DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.

i

The actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.

Connecting actuator to radio transmitters 

Load is switched off.

o

Press the 

Prog

 button for longer than 4 seconds.

The load switches on.
The status LED flashes after 4 seconds and the load switches off. The actuator is in
programming mode for approx. 1 minute.

o

Switch radio transmitter to programming mode (see radio transmitter instructions).

o

Trigger telegram on the radio transmitter.
The status LED of the actuator lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.

i

If the status LED of the actuator flashes 3 times at 1-second intervals for approx.
5 seconds, then the programming operation was not successful. All the memory locations
in the actuator or radio transmitter are occupied.

i

All On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place.

i

Scene buttons must be connected separately.

 Disconnecting connection to a radio transmitter

o

Carry out the same steps as when connecting (see Connecting actuator to radio
transmitters).
The status LED flashes quickly for 5 seconds. The actuator is disconnected from the radio
transmitter. The actuator and radio transmitter exit the programming mode automatically.

i

If there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.

i

All On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection of the corresponding output to the radio transmitter is disconnected.
Manual disconnection is not possible.

Resetting the device to the factory setting

All connections to radio transmitters are disconnected and parameters are reset to default
setting. If the operating mode switch is on 

PC

, the operating mode switching is set.

i

The connections in the radio transmitters are preserved and must be deleted separately.

Load is switched off.

o

Press the 

Prog

 button for at least 20 seconds.

The load switches on.
The status LED flashes after 4 seconds and the load switches off. The status LED flashes
faster after 20 seconds.

32581212

10499450

09.05.2016

5/11

eNet

Wireless switching/momentary-contact actuator, 1-gang Mini, Wireless
switching/momentary-contact actuator, 1-gang Mini, zero-voltage

Summary of Contents for 5423 00

Page 1: ...gerous voltage to the device or load Danger of electric shock Device is not suitable for disconnection from supply voltage Danger of electric shock on the SELV PELV installation Not suitable for switc...

Page 2: ...sible Switchable output with Prog button Status indicator via LED Switching mode of operation Switch on telegram Device switches on Switch off telegram Device switches off Operating mode buttons Relay...

Page 3: ...trical connection DANGER Electrical shock when live parts are touched Electrical shocks can be fatal Before carrying out work on the device or load disengage all the corresponding circuit breakers Cov...

Page 4: ...ion Function PC Operating mode and parameter set with eNet server M Operating mode buttons K Switching mode of operation If the operating mode switch is turned from the position PC to another operatin...

Page 5: ...actuator or radio transmitter are occupied i All On and All Off buttons of a radio transmitter are connected to the actuator automatically as soon as the first connection to the radio transmitter tak...

Page 6: ...onnection single stranded 0 75 4 mm Finely stranded with conductor sleeve 0 75 2 5 mm Dimensions H 53 28 mm Radio frequency 868 0 868 6 MHz Transmission capacity max 20 mW Transmitting range in free f...

Page 7: ...essed Flashing Switch on starts flashing and switch off stops flashing The default flash frequency is 1 Hz This frequency is also the maximum flash frequency The flash frequency can be changed using p...

Page 8: ...ot yet been switched off due to the delay when a switch on command comes then the load will remain on In Flashing operating mode the pulse times are set using this parameter Comment The set times appl...

Page 9: ...ing the switch off warning a switch on telegram effects direct switch on It is not possible to terminate the time using a switch off telegram Priority lock out protection 0 4 Basic setting 1 Specifies...

Page 10: ...on Minimum switching repeat time 100 ms 10 sec Basic setting 100 ms Limits the switching speed of the device by increasing the value in order to protect the load for example Only when the set time has...

Page 11: ...ira de konformitaet 6 5 Warranty The warranty follows about the specialty store in between the legal framework as provided for by law Please submit or send faulty devices postage paid together with an...