Troubleshooting and support
Order No. 2089 00
Page 63
13. Troubleshooting and support
The following fault tree is intended to solve the most frequent problems.
Is the orange “KNX” LED on permanently?
Brief irregular interruptions are permissible.
Check the KNX wiring and the LED status dis
-
plays.
Is the green “RUN/DIAG” LED on perma
-
nently?
Check the general release for remote access
using KNX group objects 1 and 2.
Is the green “RUN/DIAG” LED flashing regu
-
larly and slowly at 1 Hz?
Check the device parametrisation
in the ETS
Is the device visible in the Windows network
environment?
Check the network wiring and the parametri
-
sation of the IP address in the ETS.
Is the device displayed on the
Gira Device portal as online?
Check your Internet connection. If you do not
use a DHCP, check the specified DNS server.
Check the device website for other error infor
-
mation.
Check the configuration and status of the user
groups in the Gira Device portal and on the
device website.
Restart the device via the device website.
No
Yes
Yes
No
Yes
No
No
Yes
No
Yes