Page 6-11
Troubleshooting Tools
Troubleshooting and Analysis
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
18
Press
8
to display Reregulation factors. Use item 8 to review the reregulation factors. Those
will be controlled by the intelligent reregulation of monitoring and impact the vapor
performance per side. The permitted reregulation range is (85 - 125). A factor value of 100
represents 100%.
Figure 6-17: Reregulation Setup
19
Press
9
for Function Test. Do not select this function because the test procedure requires
special function test equipment and is intended to be used on the factory line end tester.
20
Press
h
to display Hot Keys.
shows all other available keys.
Figure 6-18: HotKeys