Troubleshooting and Analysis
Troubleshooting Tools
Page 6-8
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
13
Press
3
to set factory defaults. This function sets all configuration parameters to default
conditions. This item can be used if the board has an undefined malfunction.
This menu requires safety code as:
33154
. The factory defaults are:
• M1 and M2 H/V-Inputs are set default 1200 rpm
• The Pulse Ratio is set to 136 p/l
• The A/L - Ratio is set to 100%
Figure 6-11: Setting Factory Defaults
14
Press
4
to enter the Debug Mode. This submenu shows all debug mode options. Press “f” to
toggle between fuel flow debug mode ON and OFF. If the debug mode is ON the screen will
show the fuel flow rate when a transaction is running. During flow debug-mode, no other
mode can be activated.
Figure 6-12: Debugging Modes