Page 6-7
Troubleshooting Tools
Troubleshooting and Analysis
MDE-5394B VaporTEK™/VaporTEK-3 Controller Board 110 V UL® Vapor Recovery Collection System for Encore® 500 S
Start-Up and Service Manual · March 2019
11
Press
1
to display the configuration currently set.
Figure 6-9: Current Configuration
12
Press
2
to set configuration. The Set Configuration submenu shows how the motor speed value
can be assigned to HV- Signals M1 and M2 Inputs.
This menu requires this safety code:
33154
.
Once the HV Input M1 or M2 becomes active, the motor runs with the setup speed. If both
HV-Signals become active, the motor runs with the speed that is the sum of the single speed
values of M1 and M2.
If the result of speed value is higher than the max value, then the max speed (2500 rpm) will
be the setting.
Figure 6-10: Setting Configuration