GiBiDi AS05800 Instructions For Installation Manual Download Page 1

SC380

UK

SC380  (AS05800 - AS05810)

Electronic control unit

INSTRUCTIONS FOR INSTALLATION

Summary of Contents for AS05800

Page 1: ...SC380 UK SC380 AS05800 AS05810 Electronic control unit INSTRUCTIONS FOR INSTALLATION ...

Page 2: ...directive GI BI DI S r l reserves the right to modify the technical data without prior notice depending on the product development WARNING 230 Vac 42 43 44 M12 J1 J2 42 43 44 M12 J1 J2 380 Vac Thecontrolunitisprovidedwithoutjumperfortheselectionofthesupplyvoltage Before powering the control unit it is necessary to make a jumper on terminal M12 according to the supply voltage youwanttouse ...

Page 3: ...SC380 3 UK AS05800 31 6 236 1 2 8 236 31 6 AS05810 1 2 8 DIMENSIONS 1 ...

Page 4: ...4 SC380 UK INSTALLATION 2 170 250 ...

Page 5: ...ANSFORMER ELECTRICAL CONNECTIONS 42 43 44 M12 F1 J1 J2 J3 J4 J5 J6 J7 TR3 RL7 JP1 RL6 MCU RX CONNECTOR 380 220 0 14 Vac 22 Vac 0 220 Vac 380 Vac F4 F3 F2 TR2 RL8 RL5 1 A 6 A BLACK GREY BROWN RED BLUE 14 Vac 22 Vac 3 ...

Page 6: ...TR1 RL8 RL3 RL4 RL5 RL7 JP1 RL6 MCU RX CONNECTOR DL1 DL2 DL3 DL4 DL5 DL6 DL7 DL8 DL9 DL11 PED NO START NO FCA NC PHOTO 2 NC RISERVA NO SAFETY 1 NC PHOTO 1 NC COM FCC NC OPEN NO CLOSE NO SAFETY 2 NC STOP NC COM PHASE R PHASE S PHASE T COM EARTH EARTH LAMP LAMP 230Vac 40W MAX MENU E32 MENU E34 M10 M9 M11 30 31 32 33 35 34 36 38 37 39 40 41 24Vdc 3W MAX 24Vcc 24Vcc E SAV INDUCTIVE SENSOR 24Vcc COM OP...

Page 7: ...CC NC OPEN NO CLOSE NO SAFETY 2 NC STOP NC COM PHASE R PHASE S PHASE T COM EARTH EARTH M LAMP LAMP M1 M2 M3 M4 M5 M6 M7 M10 M9 M11 M8 M12 F1 F4 F3 F2 J1 J2 J3 J4 J5 J6 J7 OK ESC RL1 RL2 TR3 TR2 TR1 RL8 RL3 RL4 RL5 RL7 JP1 RL6 MCU RX CONNECTOR DL1 DL2 DL3 DL4 DL5 DL6 DL7 DL8 DL9 DL10 230Vac 40W MAX M10 M9 M11 30 31 32 33 35 34 36 38 37 39 40 41 24Vdc 3W MAX 24Vcc 24Vcc E SAV INDUCTIVE SENSOR 24Vcc ...

Page 8: ...R PHASE S PHASE T EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 M6 RL1 RL2 230Vac 40W MAX M COM CLOSE OPEN 380 Vac 5 6 7 8 1 2 3 4 9 10 11 EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 RL1 RL2 230Vac 40W MAX 12 13 14 M6 PHASE R PHASE S PHASE T M COM CLOSE OPEN AS05810 AS05800 MENU E32 MENU E34 REL1 REL2 MENU E32 MENU E34 REL1 REL2 6 ...

Page 9: ... EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 M6 RL1 RL2 230Vac 40W MAX M COM CLOSE OPEN 230 Vac 5 6 7 8 1 2 3 4 9 10 11 EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 RL1 RL2 230Vac 40W MAX 12 13 14 M6 PHASE R PHASE S PHASE T M COM CLOSE OPEN AS05810 AS05800 42 43 44 M12 J1 J2 MENU E32 MENU E34 REL1 REL2 MENU E32 MENU E34 REL1 REL2 ...

Page 10: ...2 3 4 9 10 11 PHASE NEUTRAL EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 M6 RL1 RL2 230Vac 40W MAX M COM CLOSE OPEN M COM CLOSE OPEN 5 6 7 8 1 2 3 4 9 10 11 EARTH EARTH LAMP LAMP M1 M2 M3 M4 M5 RL1 RL2 230Vac 40W MAX 12 13 14 M6 PHASE NEUTRAL AS05810 AS05800 MENU E32 MENU E34 REL1 REL2 MENU E32 MENU E34 REL1 REL2 ...

Page 11: ...0 Vac 1 2 M1 EARTH EARTH 11 12 230 Vac 3 PHASES MOTOR CONNECTION 230 Vac 1 PHASE MOTOR CONNECTION 230 Vac 5 3 4 M M2 PHASE R PHASE S PHASE T COM CLOSE OPEN M2 230 Vac 5 3 4 M PHASE R NEUTRAL N PHASE R COM CLOSE OPEN FLASHING LIGHT CONNECTION 6 7 LAMP LAMP M3 230 Vac 40W max MENU C 2 2 on off on off 3 on off on off Ref 13 ...

Page 12: ...380 UK 14 M4 MULTIFUNCTION TERMINAL BLOCK 8 9 M4 MENU E 32 Rif on off 3 sec on off 3 sec on off 3 Min on off on off on off on off on off on off 3 sec on off 3 sec 2 3 4 5 6 8 9 M4 8 9 M4 8 9 M4 8 9 M4 3 Min ...

Page 13: ...K 15 M5 MULTIFUNCTION TERMINAL BLOCK 10 11 M5 MENU E 34 Rif on off 3 sec on off 3 sec on off 3 Min on off on off on off on off on off on off 3 sec on off 3 sec 2 3 4 5 6 10 11 M5 10 11 M5 10 11 M5 10 11 M5 3 Min ...

Page 14: ...5 16 17 18 19 20 21 22 23 PED NO START NO FCA NC RISERVA NO COM FCC NC OPEN NO CLOSE NO COM M7 MENU E 9 ELECTROMAGNETIC DETECTOR CONNECTION MMD 19 PED NO START NO FCA NC RISERVA NO COM FCC NC OPEN NO CLOSE NO COM 15 16 17 18 19 20 21 22 23 M7 REED REED M1 M M4 M3 5 6 7 5 6 7 5 6 7 FCA FCC COM MOTOR OPEN MOTOR CLOSE MOTOR COM PED NO START NO FCA NC RISERVA NO COM FCC NC OPEN NO CLOSE NO COM 15 16 1...

Page 15: ... M1 1 2 3 4 M2 1 MENU C 41 23 PHOTOCELLS 1 WITH TEST CONNECTION PHOTOCELLS 2 CONNECTION PHOTOCELLS 2 CONNECTION WITH TEST MENU C 40 E1 24 25 26 27 28 29 PHOTO 2 NC SAFETY 1 NC PHOTO 1 NC SAFETY 2 NC STOP NC COM M8 M9 30 31 32 33 24Vdc 3W MAX 24Vcc 24Vcc E SAV 2 3 RX TX M1 1 2 3 4 M2 1 COM 2 3 RX TX M1 1 2 3 4 M2 1 MENU C 41 E 1 24 25 26 27 28 29 PHOTO 2 NC SAFETY 1 NC PHOTO 1 NC SAFETY 2 NC STOP N...

Page 16: ...M9 30 31 32 33 24Vdc 3W MAX 24Vcc 24Vcc E SAV 25 COM 8K2 SAFETY DEVICE 1 CONNECTION 8K2 NC NC NC 24 25 26 27 28 29 PHOTO 2 NC SAFETY 1 NC PHOTO 1 NC SAFETY 2 NC STOP NC COM M8 M9 30 31 32 33 24Vdc 3W MAX 24Vcc 24Vcc E SAV 26 COM MENU C 43 NC SAFETY DEVICE 2 CONNECTION 8K2 24 25 26 27 28 29 PHOTO 2 NC SAFETY 1 NC PHOTO 1 NC SAFETY 2 NC STOP NC COM M8 M9 30 31 32 33 24Vdc 3W MAX 24Vcc 24Vcc E SAV 27...

Page 17: ...dc 3W MAX 24Vcc 24Vcc E SAV 31 COM MENU C 44 STOP CONNECTION M9 30 31 32 33 24Vdc 3W MAX 24Vcc 24Vcc E SAV 29 COM WARNING LIGHT CONNECTION 35 34 36 37 IMP 24Vcc COM OPT M10 30 MOTOR RPM SENSOR BLUE BROWN BLACK 38 39 40 41 S3 S4 S1 S2 M11 31 2 CONTROL BOARDS SYNCHRONIZATION 38 39 40 41 S3 S4 S1 S2 M11 M8 M9 28 ...

Page 18: ... Code Electronic control unit for the automation of one 230Vac or 380Vac motor for swinging sliding gates or bollards SC380 Yes No 1 230Vac Monophase 50 60 Hz 230 380Vac Three phase 50 60 Hz 230Vac 40W max 230Vac Monophase 50 60 Hz 230 380Vac Three phase 50 60 Hz 24Vdc 3W max Managed by relay with free contact 24Vdc 8W max Safety devices power supply Plug in 20 C 60 C IP 55 Safety devices test Yes...

Page 19: ...djustablepausetime differentiatedforcompleteorpedestrianopening 4possibleworkingfunctions stepbystep stepbystepwithstop condominiumorautomatic deadman Possibilityofchoosingthesystemconfigurationbetweenswinging slidinggateandbollard Settingof5safetyinputs selectableasinputs STOP RESISTIVENC RESISTIVE8K2 PHOTO1 PHOTO2 Settingof Automaticclosing Fastclosing Pre flashing Hammerstroke Finalopeningandcl...

Page 20: ...ood technicalknowledgeandprofessionalpracticeincompliancewiththeregulationsinforcearerequired Maintenancemustbecarriedoutbyqualified personnel Beforecarryingoutanycleaningormaintenanceoperation disconnectthecontrolunitfromthemains Thiscontrolunitmayonlybeusedforthepurposeforwhichitwasdesigned The use of the product for purposes different from the intended use has not been tested by the manufacture...

Page 21: ...e Secondary 22 Vac transformer J7 6 ELECTRICAL CONNECTIONS TERMINAL BOARDS Terminal Fig Position Description 1 Ground wire connection 9 Signal GND 2 M1 3 4 M2 5 Motor Motor connection Motor connection Motor connection 10 6 7 M3 Lamp 230 Vac 40 W flashing light output 13 11 12 Menu C2 8 9 M4 REL1 Menu 32 Free contact NO 14 Menu E 32 10 11 M5 REL2 Menu 34 Free contact NO 15 Menu E 34 12 230 Vac 380 ...

Page 22: ...Photo 2 Default Menu C41 not active 26 Programmable safety device input Safety 1 Default Menu C42 not active 27 Programmable safety device input Safety 2 Default Menu C43 not active M8 28 Programmable safety device input Stop Default Menu C44 STOP 29 COM 28 29 30 Warning light output 24 Vdc 3W Synchronized with Warning light Flashing light during the motion and on with 31 Power supply 24 Vdc exter...

Page 23: ...or 36 COM Inputs common Outputs and Negative 24 Vdc 37 OPT Not used M10 30 38 Synchronization connection S1 39 S2 40 S3 41 S4 with another one SC 380 M11 31 42 Transformer connection for power supply Transformer 43 M12 6 at 230 Vac Transformer common Power supply Transformer connection at 380 Vac 44 7 8 6 ELECTRICAL CONNECTIONS TERMINAL BOARDS ...

Page 24: ...led and PEDESTR DL 2 GREEN Turns on when the OPEN command is enabled off at release and turns OPEN DL 3 GREEN Turns on when the CLOSE command is enabled off at release and turns CLOSE DL 4 RED Always turned on It turns off when reaching the LIMIT SWITCH of the motor OPENING FCA DL 5 RED Always turned on It turns off when reaching the LIMIT SWITCH of the motor CLOSING FCC DL 6 RED Turns on when the...

Page 25: ... is in pause phase The CLOSE inscription indicates that the gate is in closing phase This display indicates that the contats of reference 24 25 26 27 28 areclosedorexcluded This display with letters indicates that the contacts of reference PHOTO 2 25 andSTOP 28 areopened This display with blinking asterisk indicates that the contacts of reference PHOTO 2 25 and STOP 28 have intervened during the m...

Page 26: ...ing a value Thebutton ESC isofusefor movingfromsub menustomainmenus goingoutfromtheprogrammingpushing ESC for3sec The button OK is of use for entering the menus confirming and storing the values set Button to enable the PEDESTRIAN command Button ESC is not enabled Button OK is enabled to activate STOP command Button is enabled to activate START command Atrestthebuttonshavethefollowingfunctions OK ...

Page 27: ...aticreclosing E94 firmwareversion ByDEFAULTPASSWORD 1234 youenteralltheMENUS ThePASSWORDiscustomizablebytheMENUE92 thenewPASSWORD w i l l d i s a b l e t h e u s e o f D E FA U LT PA S S W O R D S The DEFAULT PASSWORDS can be recovered making a reset of the controlunit ESC OK With control unit at rest press the buttons ESC and OK at the same time for3seconds itwillimmediatelyappearMENU thenPASS To...

Page 28: ...ESC OK Maketheaccesstotheprogrammingasdescribedinchapter11 Pressthebutton todisplaythenumber 1 Pressthebutton OK toconfirm Thebutton ESC isnotenabledtillPASSWORDconfirmation Theseconddigitwillblink Pressthebutton OK toconfirm usethebutton tilldisplaythenumber 2 Thethirddigitwillblink usethebutton tilldisplaythenumber 3 Pressthebutton OK toconfirm Thefourthdigitwillblink usethebutton tilldisplaythe...

Page 29: ...4isfinished 14 PROGRAMMING EXAMPLE OF SETTING E9 4 Maketheaccesstotheprogrammingasdescribedinchapters11and13 Usethebuttons or toscrolltheletters stopwhen E blinks Pressthebutton OK Usethebuttons or toscrollthesub menus stopwhen E91 isdisplaied Thebutton ESC isenabledonlytocomebacktothepreviousMENU TheprocedureusedinthisexampleforMENU E isvalidfor MENUS A C also ESC OK AC HE AC HE E1 1 E9 1 E9 1 E9...

Page 30: ...n ESC is enabled only to come back to the previous MENU Pressthebutton OK theseconddigitwillstart blinking WARNINGInthisphasethebutton ESC isnotenabled Usethebutton OK tillmakingthedigityoumustmodifyblink Use the buttons or to increase or decrease the value till displaying 0020 Pressthebutton OK TheprogrammingofH2 20isfinished The procedure used in this example for MENU H is valid also for MENU E ...

Page 31: ...tons and atsametimefor3seconds CRTE willappeartoindicatethattheprocedurehashadasuccessfulconclusion The displaywillshowtheopeningscreen Theresetprocedureisfinished It is possible to make a reset of the control unit to come back to factory parameters WARNING all the settings done will be lost except the ones concerning performedcyclesandpowersupplydays ESC OK 17 RESET PROCEDURE ESC OK ESC OK AC HE ...

Page 32: ...C4 C10 C11 C13 are not visible any more active the electronic brake 3 A 3 STEP BY STEP WITH STOP LOGIC 2 ItenablestheSTEPBYSTEPWITHSTOPLogic OperationafteraSTARTcommand Closegate OPEN Duringopening STOP Opengate CLOSE Duringclosing STOP Aftera STOP invertthemotion Configures the installation for rising bollard using the additional control unit BX 6M AS07010 With this configuration il will be autom...

Page 33: ...es the total automatic closing See Menu H9 the pedestrian automatic closing See Menu H11 2 It enables only the total automatic closing See Menu H9 3 It enables only the pedestrian automatic closing See Menu H11 4 STEP BY STEP LOGIC 3 ItenablestheSTEPBYSTEPLogic OperationafteraSTARTcommand Closegate OPEN Duringopening CLOSE Opengate CLOSE Duringclosing OPEN AUTOMATIC CONDOMINIUM LOGIC 4 It enables ...

Page 34: ...ashinglightandmotorwillstartatthesametime 1 Itenableslthepre flashingfunction Theflashinglightwillstart3secondsbeforemotorstart 2 PREFLASHING C 3 It disables the limit switch reading 1 It enables the limit switch reading 2 LIMIT SWITCH C 4 It disables the hammer stroke function 1 It enables the hammer stroke function in opening to help the releaseoftheelectriclock seemenuE32andmenuE34 Operation Af...

Page 35: ...ed with sliding configuration andisnotadvisedwith electromechanicaloperators 3 HAMMER STROKE C 10 It disables the final stroke in closing function 1 FINAL STROKE IN OPENING AND CLOSING C 11 2 Itenablesthefinalstrokeinopeningandclosing Operation At the end of closing or opening manoeuvre the gate motioncontinuesfor 2secondsmore Thefinalstrokeisnotcontrolledbysafetydevices Notactivewithslidingconfig...

Page 36: ...draulicblockmaintenance function 1 1 It enables the Hydraulic block maintenance function Operation As previous selection but every 3 HOURS 3 It enables the Hydraulic block maintenance function Operation As previous selection but every 5 HOURS 4 HYDRAULIC LOCK UPKEEP FOR HYDRAULIC OPERATORS ONLY C 13 Itenablesthe MANUALcheckoftheOPENINGlimitswitch Moving the gate by hand towards opening the flashin...

Page 37: ...C1 programming of SAFETY DEVICES No 1input terminal 24 named PHOTO 1 C 40 3 4 InputprogrammedasPHOTOCELL2 Operation Inputactivebothinopeningandclosing If intercepted it stops the motion and keeps it blocked till when itisnotfreed Atreleasethemotionrestartsalwaysinopening Ifinterceptedinpause itreloadsthepausetime InputprogrammedasEDGE8K2 Operation obstaclefreeingway OPEN CLOSE themotionrestartsino...

Page 38: ...itreloadsthepausetime Ifenabled itallowsthefastclosing seemenuC1 InputprogrammedasPHOTOCELL2 Operation Inputactivebothinopeningandclosing If intercepted it stops the motion and keeps it blocked till when itisnotfreed Atreleasethemotionrestartsalwaysinopening Ifinterceptedinpause itreloadsthepausetime Input programmed as EDGE 8K2 Operation obstacle freeing way OPEN CLOSE the motion restarts in open...

Page 39: ... itreloadsthepausetime Ifenabled itallowsthefastclosing seemenuC1 InputprogrammedasPHOTOCELL2 Operation Inputactivebothinopeningandclosing If intercepted it stops the motion and keeps it blocked till when itisnotfreed Atreleasethemotionrestartsalwaysinopening If interceptedinpause itreloadsthepausetime Input programmed as EDGE 8K2 Operation obstacle freeing way OPEN CLOSE the motion restarts in op...

Page 40: ...eloadsthepausetime Ifenabled itallowsthefastclosing seemenuC1 InputprogrammedasPHOTOCELL2 Operation Inputactivebothinopeningandclosing If intercepted it stops the motion and keeps blocked till when it isnotfreed Atreleasethemotionrestartsalwaysinopening Ifinterceptedinpause itreloadsthepausetime Input programmed as EDGE 8K2 Operation obstacle freeing way OPEN CLOSE the motion restarts in opening o...

Page 41: ...sthepausetime Ifenabled itallowsthefastclosing seemenuC1 InputprogrammedasPHOTOCELL2 Operation Inputactivebothinopeningandclosing If intercepted it stops the motion and keeps it blocked till when itisnotfreed Atreleasethemotionrestartsalwaysinopening Ifinterceptedinpause itreloadsthepausetime Input programmed as EDGE 8K2 Operation obstacle freeing way OPEN CLOSE the motion restarts in opening or c...

Page 42: ...t determines the pause time before the automation restarts the motion that had been interrupted after an intervention of the EDGE and or the MOTOR REVOLUTIONS SENSOR see menu E30 0 60 seconds adjustable at intervals of 1 second 10 WAITING TIME FOR REPEATED ATTEMPTS AFTER SAFETY DEVICES INTERVENTION H 19 DESRCIZIONE MENU A 18 4 DESCRIPTION MENU E Menu Function Description Status it disables the pho...

Page 43: ...on If the test fails an anomaly is signalled by some blinkingsoftheflashinglight seechapter23 2 SAFETY DEVICES TEST SET AS EDGE E 3 ENERGY SAVING EXCLUDED 1 ENERGYSAVINGENABLED Operation 24Vdc on terminal 32 will be present only during the operation cycle Connecting the external accessories to this terminal you can have a significant energy saving during the rest phase of the gate Withthisfunction...

Page 44: ...tion of an externalclock amagneticlooporadifferentcommand Operation When the contact on the RESERVE input is close after a START command the door will open but will not close automatically Whenthecontactisopen thedoorwillcloseautomaticallyafter pausetime It is not possible to enable the closing with START command andCLOSINGbutton WARNING remindtoenabletheautomaticclosing 3 It enables the RESERVE i...

Page 45: ...TS to restart the motion after the intervention of the devices set as EDGE and of the MOTOR REVOLUTIONS SENSOR E 30 As set 1 but 3 attempts are made 3 As set 1 but 4 attempts are made 4 As set 1 but 5 attempts are made 5 WARNING A programming of the function different from the configuration preset from the manufacturer although it allows if correctly done the reduction of the cases of stop of the ...

Page 46: ...eginning of opening and closing set as electric magnet Turned off for 3 seconds at the 6 REL1 management Terminals 8 9 FREE CONTACT Fig 14 E 32 REL2 set as electric lock Enabled for 3 seconds at the beginning of opening and closing 2 REL2 set as Enabled for 3 minutes more after motor stop courtesy light 3 REL2 Synchronized blinking with LAMP 230V fixed or intermittent output set as flashing light ...

Page 47: ...ew Start pulse is given the motion starts again in the directionofobstaclefeeeing DisabledwithDEADMAN SeealsoMENUE30 2 MOTOR REVOLUTIONS SENSOR INDUCTIVE SENSOR E 36 It enables the reading of the motor revolutions sensor HIGH intervention sensitivity Operation As the previous menu 3 It enables the reading of the motor revolutions sensor MEDIUM intervention sensitivity Operation As previous menu 4 ...

Page 48: ...UT THE INTERVENTIONSNUMBERISSETTOZERO Interventions number DISPLAY OF SETTING AND INTERVENTION NUMBER OF SAFETY INPUT No 1 TERMINAL 24 E 40 It allows to display the setting of terminal 25 defined with menu C41 andthenumberofsafetyinterventions determinedbythe inputifsetasEDGE N C orasEDGE8K2 Operation See E40 E 41 It allows to display the setting of terminal 26 defined with menu C42 andthenumberof...

Page 49: ...SSWORD you can acceed to the programming PASSWORD E 92 It shows the firmware version installed on the control unit XX__YY FIRMWARE VERSION E 94 Numberofmanoeuvresdone Thevaluedisplaiedisincreasedevery10manoeuvres NUMBER OF CYCLES DONE E 96 It allows to display the setting of terminal 27 defined with menu C43 andthenumberofsafetyinterventions determinedbythe inputifsetasEDGEN C orasEDGE8K2 Operatio...

Page 50: ...hemtoterminal24 MenuC10 HAMMERSTROKE thesameonbothcontrolunits MenuE1 TESTPHOTOCELL1 thesameonbothcontrolunits MenuE3 TESTSAFETYDEVICES thesameonbothcontrolunits MenuE9 RESERVEINPUT thesameonbothcontrolunitsandparallelconnectionsonbothcontrolunits MenuH9 thesameonbothcontrolunits Thefirstcentralthatstartstheclosingcommandsalsotheotherone WARNING In case of intervention of safety devices EDGE STOP ...

Page 51: ...tional control unit BX 6M AS07010 for which you have to look up the relevantmanualfortheconnections The SC380 BX 6M system allows to control up to six single engine rising bollards or three twin engined rising bollards and allows to control all the rising bollards at the same time or only a group chosen by the switch SW1 presentonBX 6M The signals Ped terminal16 Reserve terminal 21 Open terminal 1...

Page 52: ...TART command at the beginning of closing 3 slow flashings Door blocked open Test photo 1 failed at the beginning of closing 4 fast flashings Door blocked open Test photo 2 failed at the beginning of opening 3 fast flashings Door blocked close Test photo 2 failed at the beginning of closing 3 fast flashings Door blocked open Test edge N C failed at the beginning of opening 3 slow flashings Door blo...

Page 53: ...0 Are in conformity with the following CEE Directives LVDDirective2006 95 CEandsubsequentamendments EMCDirective 2004 108 CEandsubsequentamendments and that the following harmonized standards have been applied EN60335 1 EN60335 2 103 EN50366 EN61000 6 2 EN61000 6 3 Date 10 07 2019 S r l eclares that the products The legal Representative Michele Prandi ...

Page 54: ...54 SC380 UK NOTES ...