21
Flow rates
: This menu entry is the air flow rate submenu.
Flow
rate
Norm.
:
Att.
:
Exch.
140
90
Room
240
200
FreeC. 220
180
The setting can be entered separately:
-
exchange flow rates (Exch.) from 90 to 220 m3/h;
-
room flow rates (Room), from 220 to 360 m3/h;
All flow rates can be set in the normal (Norm.) or attenuation mode (Att.).
Summer Delivery Temp.
Air delivery temperatures in summer mode, one for the neutral air
function and one for the cooling integration function.
Winter Delivery Temp.
Air delivery temperatures in winter mode, one for the neutral air
function and one for the heating integration function.
Temp. Free-Cooling:
temperatures that limit the free-cooling mode.
The Free-Cooling mode fails:
-
below MinWinter;
-
above MaxWinter;
-
above MaxSummer in summer.
Season source:
To decide if the season must be entered by digital input or keypad;
Compress. in Att.:
To decide if the compressor must be ON or OFF during attenuation.
Generally, the attenuation function is used to reduce the noise form the unit; in this case it
can be useful to stop the compressor.
F.C. External Temp.:
MinWinter:
8 °C
MaxWinter: 20 °C
MaxSummer: 25 °C