12
SUMMER, dehumidification/integration during recirculation (300m3/h)
room
condition
°C - %RH
delivery
water
temp.
°C
cooling power
power required by
water cooling
cooling
compress
or electric
power
total
W*
sensible
W
latent
W
latent
W
l/day
W
dehumidific
ation
W
int. max
24 – 55
12
15
18
2128
1784
1463
1455
1305
1172
673
479
291
23,2
16,5
10,1
1129
954
785
2552
2232
1933
426
448
470
24 – 65
12
15
18
2372
1967
1622
1358
1189
1051
1014
778
571
35,0
26,9
19,7
1479
1264
1075
2800
2420
2098
428
453
476
26 – 55
12
15
18
2461
2022
1710
1574
1390
1265
887
632
445
30,6
21,8
15,4
1354
1119
950
2889
2475
2185
428
453
475
26 – 65
12
15
18
2740
2324
1896
1470
1301
1137
1270
1023
759
43,9
35,3
26,2
1747
1519
1275
3171
2780
2377
431
456
481
SUMMER, ex recirculation (160m3/h 35 °C 55% + 140 m3/h recirculation)
room
condition
°C - %RH
delivery
water
temp.
°C
cooling power
power required by
water cooling
cooling
compress
or electric
power
total
W*
sensible
W
latent
W
latent
W
l/day
W
dehumidific
ation
int. max
W
24 – 55
12
15
18
3257
2832
2391
1866
1694
1525
1391
1138
866
48,1
39,3
29,9
1953
1720
1467
3166
2767
2351
431
457
482
24 – 65
12
15
18
3358
2945
2504
1818
1654
1488
1540
1291
1016
53,2
44,6
35,1
2107
1877
1621
3270
2881
2465
434
458
483
26 – 55
12
15
18
3369
2952
2511
1906
1741
1575
1463
1211
936
50,5
41,8
32,3
2017
1784
1529
3375
2982
2567
434
458
484
26 – 65
12
15
18
3523
3086
2640
1870
1699
1534
1653
1387
1106
57,1
47,9
38,2
2212
1965
1703
3530
3118
2697
435
460
485
SUMMER, ex recirculation (160m3/h 35 °C 55% + 140 m3/h recirculation)
room
condition
°C - %RH
delivery
water
temp.
°C
cooling power referred to the internal
environment**
total*
sensible
W
latent
W
latent
W
l/day
\\
12
1626
1239
387
13,4
24 – 55
15
18
1203
761
1068
899
135
-138
4,7
-4,8
12
1984
1195
789
27,3
24 – 65
15
1571
1031
540
18,7
18
1131
865
266
9,2
12
2027
1392
635
21,9
26 – 55
15
1611
1227
384
13,3
18
1169
1061
108
3,7
12
2473
1361
1112
38,4
26 – 65
15
2037
1190
847
29,3
18
1590
1025
565
19,5
*The total cooling power
comes from the
recovered heat, the pre-
treatment coil and the
direct expansion coil.
**The cooling power
referred to the internal
environment is generated
by the difference between
the inflow air enthalpy and
the room air enthalpy.
Negative values indicate
that the unit cannot
sustain the desired
conditions even without
internal loads.