11
TECHINCAL DATA
Electric power
V/Ph/Hz
230/1/50
Weight
kg
85
Total dehumidification capacity
(external environment 35 °C, 50% R.H.)
l/24h
56
W
1620
Useful dehumidification capacity
(referred to recirculation, room at 26 °C, 55% R.H.)
l/24h
25
W
723
Useful cooling capacity (referred to
recirculation, room at 26 °C, 55% R.H.)
W
1460
Nominal electric power absorbed
W
820
Electric power absorbed by the compressor
W
470
Water flow rate required
l/h
360
Water circuit loss of pressure
kPa
12
Power absorbed by the delivery fan (min - max)
W
40 - 170
Delivery fan flow rate (min - max)
m3/h
90 - 360
Delivery fan useful hydraulic head
Pa
200
Power absorbed by the ejection fan (min - max)
W
40 - 170
Ejection fan flow rate (min - max)
m3/h
90 - 360
Ejection fan useful hydraulic head
Pa
200
Energy recovery during winter operation
(20 °C - 50% internal r.h., -5 °C - 80% external r.h.)
flow
rate 90
m3/h
91%
flow
rate 220
m3/h
87%
Energy recovery during summer operation
(26°C - 65% internal r.h., 35°C - 50% external r.h.)
flow
rate 90
m3/h
89%
flow
rate 220
m3/h
82%
Sound pressure level (in open field, distance 1m)
dB(A)
42