BA230
53
UK
E9
E90
E92
E94
E96
E98
EXTERNAL CLOCK
CYCLES NUMBER
INSTALLER CODE
FIRMWARE RELEASE
NUMBER OF PERFORMED
CYCLES
NUMBER OF POWER SUPPLY
DAYS
4
EXTERNAL CLOCK - AUTOMATIC OPENING AND CLOSING
COMMAND
Enables the RESERVE input for the connection of an external clock.
Operation:
with the closed contact on the RESERVE input, an automatic opening
command will activate (with no need of a START command).
The door will open, but it will not close automatically.
Following the contact closing, the door will close automatically after
the pause time.
It is not possible to activate the closing with the START command.
WARNING
: remember to preset the automatic closing
Allows the setting of a number of cycles ( closing) before
the maintenance request.
The value set will always be multiplied for 10.
If 0000 is set, the numbering is excluded.
When the set number of cycles is reached, the maintenance request
is signalled by a slow blink of 60 sec. at the end of the movement.
The signalling will be blinking even if the C2 menu is set up with
fixed light.
WARNING: Each time you enter in E90 menu (WITH BLINKING
NUMBERS, THAT MEANS READY TO BE MODIFIED) the count
of the cycles number resets starting from the beginning.
Allows the input of the installer code to customize the settings during
the programming phase.
The INSTALLER CODE is the only way to enter the programming
menu.
Shows the firmware release installed on the equipment. (XX_YY)
Number of performed cycles. The value displayed on the LCD screen
is increased every 10 movements.
Number of control unit power supply days.
The data increments when the 24 hours expire.
Possible lacks of power supply reset the count of last day
T3 ADDITIONAL TIME
TIMES LEARNING PROCEDURE
Additional time at the end of the working time (with full force or during deceleration phase according to the
settings) that allows to continue the closing movement even if there is wind.
The T3 function is disabled with the sliding configuration.
WARNING
: start with the gate completely closed.
During the times self-learning phase, motion always occurs at a non-decelerated speed.
If decelerations are needed, stop the leaves before the stroke, then remember to enable the decelerations option
(menu C5) and set the decelerations times (menu H3 and H6).
During the times self-learning phase the limit switches are not considered.
Times are programmed by means of sequences of START pulses.