ERROR – Error:
If using S
3
L flow sensor, activates relay when no
sensor is detected.
MULTIPLE – Multiple Mode:
Activates relay when any one of the four enabled
conditions are met. User can select from Missing
Signal, Overrun, High Flow or Error.
TOT VOL – Totalizer Volume:
When resettable totalizer exceeds specified volume,
relay activates and latches.
Requires Totalizer Volume Reset to deactivate relay
(see Reset Total,
page 18).
This mode is useful to trigger a reminder when a
process is due, as for a backwash cycle or filter
change.
TWO STG – Two Stage:
This function is designed to prevent overfilling or
to minimize water hammer. Both the mainline relay
and the bypass relay are energized when the batch
starts. The mainline relay then de-energizes at a
programmed batch percentage, allowing flow to
continue through a smaller bypass line to reduce the
fill rate (see diagram). After the batch is dispensed,
the bypass relay de-energizes, completing the
sequence.
NOTE:
If Relay 1 is selected for Two-Stage operation,
relay 2 defaults to Bypass. If Relay 2 is selected,
relay 3 defaults to bypass. If Relay 3 is selected,
relay 2 defaults to bypass.
Advanced Mode
(See Input Menu - Page 19)
flow
to tank
Bypass valve
Main line
Valve
Bypass Piping
0%
0%
100%
0%
100%
0%
100%
Overrun
90% 100%
Relay 2 Bypass
Relay 1 Main
Time
0%
Flow Input
X
Time
Time
Time
Time
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
0%
0%
100%
0%
100%
0%
100%
Overrun
90% 100%
Relay 2 Bypass
Relay 1 Main
Time
0%
Flow Input
X
Time
Time
Time
Time
Hysteresis
Time
Process
Hysteresis
Time
Low Setpoint
Process
Time
High Limit
Hysteresis
Low Limit
Process
High
Setpoint
Relay energized
Relay de-energized
% Batch Percentage
Window
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
Relay Mode Settings