9900-1BC Batch Controller Manual
Stand-alone application
Connection to a 4 to 20 mA device
The 9900 MUST be powered by 10.8-35.2 VDC ONLY.
CAUTION
!
DO NOT connect your 9900 to AC power.
+
–
+
–
+
–
Power
Supply
12 to 32 VDC
±10%
4 to 20 mA
Device
9900
Terminals
Blue
Black
Red
Black
Red
PWR +
PWR –
Loop +
Loop –
PWR +
PWR –
Loop +
Loop –
9900
Terminals
Power
Supply
12 to 32 VDC
±10%
+
–
+
–
+
–
Power
Supply
12 to 32 VDC
±10%
4 to 20 mA
Device
9900
Terminals
Blue
Black
Red
Black
Red
PWR +
PWR –
Loop +
Loop –
PWR +
PWR –
Loop +
Loop –
9900
Terminals
Power
Supply
12 to 32 VDC
±10%
Common
Start
Stop
Resume
Inhibit*
*Wire an external input as override
for preventing batch from starting.
Connect an external button or keypad (not supplied)
to remotely control the 9900-1BC by wiring the
Batch Module as shown.
3-9900.397
Batch Module
Start
Resume
Common
Stop/Inhibit
9900 Batch Controller Module
revised 12/18/2012
Full Scale
Power Wiring
Batch Module Wiring
Sensor Wiring
2580
• When choosing
Frequency
in the Bluetooth
®
App,
the 2580 outputs an open collector frequency
signal that can be connected to the 9900-1BC.
• 24 VDC power at 1 amp should always be
connected.
NOTE: The frequency output will be displayed as
positive fl ow regardless of the fl ow direction.
24 VDC @ 1A min.
Power Supply
–
+
2580
Ground - (White)
Data (Red)
Output cable
Black
Brown
Shield
Blue not used
Not used
2580
Power cable
Black
Red
Shield (EMC enhancement)
Choose Frequency in
Bluetooth
®
App
Note:
The minimum remote push duration should be
0.5 seconds with a 1 second spacing between
button pushes..