TSA 160 NT and variants
35
Electrical installation and device settings
7.3 Entries on the identification plate
Before commissioning of the swing door system set up, markings must be made on the identification plate.
à
The entries are also required for configured drives.
à
If electrical commissioning does not directly following drive installation, the spring must be set to the smal-
lest pre-load in order to move the drive to low-energy function in accordance with the requirements of the
Machinery Directive.
à
Within electrical commissioning, the door closing torque of the power storage device must be set in accordance
with intended use of the door system as a (fire protection/personal protection door), see chapter 7.2.4.
X
Enter the correct marking on the identification plate.
Position of the plates on the TSA 160 NT
1
"Ü" symbol
2
Identification plate
1
2
3
8
5
6
4
7
a
Drive type (first character)
1
Swing door drive (classification factory provided)
s
Durability of the drive (second character)
2
500,000 test cycles, with at least 2,400 cycles/day
d
Type of door design (third character)
1
Swing door (classification factory provided)
f
Suitability as a fire protection door (fourth character)
A distinction is made between four classes of fire protection doors:
0
Not suitable as fire protection door
1
Suitable as smoke protection door
2
Suitable as fire protection door
3
Suitable as fire and smoke protection door
Note: Only one class may be specified.
g
Safety devices on the drive (fifth character)
2
Connection for external safety systems which have been approved by the drive manufacturer