GEZE SecuLogic emergency exit system
1s
t l
ev
el 2nd level
3rd level
4th level
5th level
6th level
Selection
(factory setting)
Comments
Activ. direct
Contact closes when the emergency push but-
ton is pressed on the TZ 320.
Activ. indirect
Contact closes with indirect disconnection.
Door alarm
Contact closes when the door hold-open time
is exceeded, the pre-alarm time has elapsed
or the door is broken open.
Sabotage alarm
Contact closes when an input sabotage
becomes active or if a sabotage contact is trig-
gered on TZ 320, KL 220, SCT 320 or T 320.
Pre-alarm
Contact closes for the set time when the door
hold-open time is exceeded.
System fault
Contact closes with system fault.
Signal lamp red
When interlocking door system function is ac-
tivated: Contact is closed when door is blocked
by interlocking door system.
Signal lamp green
When interlocking door system function
is activated: Contact is closed when door is not
blocked by interlocking door system.
TOE fail-secure
Contact closes for 3 seconds when short-time
unlocking has been triggered (even if system
is unlocked).
In the case of disconnection or emergency
unlocking the contact remains closed until the
alarm is ended.
Locked
Contact is closed when the system is locked.
Emergency push
button
Contact is closed as long as the emergency
push button on TZ 320 is pressed.
Short-time
unlocking
Contact is closed when the system is short-
term unlocked.
Group alarm
Contact closes when an alarm is triggered
on the bus line of a door control unit (except for
pre-alarm).
Group mess.
locked
Contact closes when all the door control units
on the bus line are locked.
Group mess.
closed
Contact closes when all the door control units
on the bus line are closed.
Group fault
Contact closes when a fault is queued on the
bus line of a door control unit.
External alarm
Contact closes during alarms for the set alarm
time.
External alarms behave in the same way as the
internal buzzer of TZ 320.
Type of contact
TZ1
Selection
Normally closed
contact
Normally open
contact
Deactivated
NC
NO
no activation of the output
The configurations are explained for the nor-
mally open contact type of contact.
For outputs with changeover contacts, the nor-
mally open contact type of contact is shown on
the wiring diagram.
If an output is configured as a normally closed
contact, it takes approx. 1 s for the normally
closed contact type of contact to be activated
after switch-on.
Delay
Selection
0 s
…
5 s
Only at control unit output 1:
Activation of the output is delayed, deactiva-
tion is immediate. If activation drops during
the delay time, the output is not activated.
Activation
Output
Delay
Activation
Output
Delay
Control unit
output 2
Configuration
TZ2
Selection
TOE fail-secure
cf. Control unit output 1
Type of contact
TZ2
Selection
Normally open
contact
cf. Control unit output 1