35
GEZE SecuLogic emergency exit system
7.3 External / central emergency push button
With indirect disconnection
à
one or more external emergency buttons which release the locking mechanism safely when actuated can be
switched in the safety circuit of a door control unit,
à
one or more central emergency push buttons which release all door control units safely when actuated can be
switched in the safety circuits of several door control units.
Indirect disconnection is activated with the jumpers J1 and J2 of TST 32x, remove the wire bridge installed be-
tween terminals 7 and 8 in the state of delivery:
no indirect disconnection (factory setting)
J1
J2
3
4
2
1
GND
indirect disconnection
indirect disconnection
7
1
8
TST 32x
X5
24V 2
indirect disconnection
J1
J2
3
4
2
1
GND
indirect disconnection
indirect disconnection
7
1
8
TST 32x
X5
24V 2
Route the normally closed contacts of the emergency push buttons in two separate lines. In the connection space
for the emergency push buttons additionally insulate the wires to the normally closed contact with insulating hose.
If there are several emergency push buttons, connect the lighting in parallel and the normally closed contacts
in series.
7.3.1 External emergency button
For the position of the external emergency button on the door see 6.1
Mount an emergency exit sign directly next to the external emergency button.
The arrow on the emergency exit sign must be pointing towards the emergency push button.
7.3.1.1 Emergency push button NOT 220
Heed the supplementary sheet for the emergency push button NOT 220.
24V
GND
indirect disconnection
indirect disconnection
7
1
2
8
1
2
X2 (+)
2
1
X2 (-)
Lighting
NC
TST 32x
X5
NOT 220
1
Line 1
2
Line 2
EltVTR