14
GEZE SecuLogic emergency exit system
5.3 Emergency push button NOT 320
5.3.1 Power supply
Power supply
24 V DC, ±10%
5.3.2 Installation
UP variant
in UP box: Diameter 60 mm, depth 62 mm
AP variant
in AP-housing: 80 mm x 80 mm x 64 mm (W x H x D)
5.3.3 Terminal assignment
1
2
X1
8 8
9 9
3
1
4 5
X3
X4
X2
X5
10 6
7 7
1
Emergency push button illuminated
2
Sabotage contact
Terminal panel
Terminal
Function
X1
1
GND
3
24VDC (supply)
4
SA
5
SA
X2
7
COM1
7
COM1
X3
8
NO2 (8 and 8 together max. 1A, 30 VDC)
8
NO2
X4
9
COM2
9
COM2
X5
10
NC1 (10 and 6 together max. 1A, 30 VDC)
6
NC1 with terminating resistor 2 kΩ (10 and 6 together max. 1A, 30 VDC)
5.4 Door terminal T 320
5.4.1 Power supply
Power supply
24 V DC, ±10%
5.4.2 Installation
UP variant
in UP boxes: diameter 60 mm, depth 62 mm
AP variants
in AP-housing: 77 mm x 197 mm x 88 mm (W x H x D)