IQ lock AUT, EL / EL DL, EM / EM DL, C / C DL, M / M DL
44
Maintenance and CE marking
6
Maintenance and CE marking
Lock maintenance work must be carried out once a year by GEZE or an authorised GEZE partner.
Maintenance instructions
These maintenance instructions are part of the installation and operating instructions and have to be made avail-
able to the owner/operator of the building.
In addition, we recommend monthly checks on the locks by the owner/operator as follows:
à
Make sure by inspecting and activating the emergency exit device that all parts of the lock are in a satisfactory
operating conditions.
à
Use a dynamometer to measure and record the operating forces required to release the panic exit device/
emergency exit lock.
à
Ensure that the operating forces have not changed substantially in comparison to the operating forces record-
ed during initial commissioning.
à
Ensure that bolt heads or keepers are not blocked or clogged up.
à
Ensure that the panic exit device has been lubricated according to the manufacturer's instructions and that
the operating element has been tightened properly.
à
Ensure that no additional locking devices are added to the door after initial installation.
à
Check whether all the components of the panic exit device still comply with the list of approved components
originally supplied with the system.
à
Ensure that these documents are made available to the owner/operator of the panic exit device/escape door lock.