Installation and commissioning.
GCLR-I 2000/GCLR-O 2000
14
DIP switch 2: Interface
On
Settings can be made in the configuration software via the RS232
interface on the reader
Off
System is in operation
DIP switch 3: Mode of operation
On
The reader can be operated both in the "networked" and "stand-
alone" mode of operation
The GCLR recognises automatically whether a GCDU 200 is connected via
the RS485 interface of the reader and then switches to networked opera-
tion.
DIP switch 4: LF field of detection
On
LF scanned field is only transmitted if the input "OPTO-IN1" is
activated
Off
The LF scanned field is transmitted permanently
12-35
V DC
–
+
IN 1
OPTO
+
–
COM
NO
1
2
3
1
Terminal panel 2
2
Terminal panel 1
3
Push button/switch for activating/deactivating the LF scanned field
DIP switch 5: Door release time
Off
The outputs switch as long as the transponder is within the
scanned field (standard). The door release time only starts running
when the transponder leaves the field. The door release time is 2 s
and can be modified using the configuration software.
On
In the "Single (2 sec.)" position, the outputs switch only once for the
set door release time when a transponder enters the scanned field.
The outputs do not switch again until the transponders have left and
reentered the scanned field.