64
5 -
T
ECHNICAL DATA TABLE
MODELS
3300
4000
INPUT
Nominal voltage
[Vac]
220 / 230 / 240
Accepted range
[Vac]
0 ÷ 276
Voltage range ruling out battery intervention
[Vac]
[Vac]
[Vac]
Maximum: 276
Minimum: 164 ÷ 84
(from 100% to 50% of load in
linear
mode)
Return to mains-powered operation: 180
Nominal frequency
[Hz]
50 - 60 +5
Maximum current
(1)
[A]
15 16
Nominal current
(2)
[A]
11 12
Power factor
≥
0.98
Current distortion @ maximum load
≤
7%
BYPASS
Accepted voltage range for switching
[Vac]
180 ÷ 264
Accepted frequency range for switching
Frequency selected ±5 %
Switching time
[msec]
Typical: 2 - Maximum: 4
BATTERY
Back-up time
[min / W]
6’ / 2300
5’30 / 2400
No. batteries / V / Ah
9 / 12 / 7 high rate discharge
Recharge time
[h]
4 ÷ 8
OUTPUT
Nominal voltage
(7)
[Vac]
220 / 230 / 240 ±1.5%
Static variation
(3)
1.5%
Dynamic variation
(4)
≤
5% in 20 msec
Waveform Sinusoidal
Voltage distortion @ linear load
≤
3%
Voltage distortion @ distorting load
≤
6%
Frequency
(5)
50 or 60 Hz selectable
Current crest factor
≥
3 : 1
Nominal power
[VA]
3300
4000
Nominal power
[W]
2300
2400
MISCELLANEOUS
Leakage current to earth
[mA]
≤
1
AC/AC efficiency
92%
Ambient temperature
(6)
[°C]
0 – 40
Humidity
< 90% non-condensing
Protections
Excessive battery discharge – Overcurrent – short-circuit
– Overvoltage – undervoltage - thermal
Safety compliance
EN 62040-1-1, directives 73/23/EC and 93/68/EC
EMC compliance
EN 50091-2 cl.B directives 2004/108/EC, 93/68/EC and
89/336/EC
Hold-up time
[msec]
≥
40
Noise level
< 40 dB(A) at 1 mt.
Dimensions H x L x D
[mm]
455 x 175 x 520
Weight [Kg]
38
38
Summary of Contents for 3300 VA
Page 2: ......
Page 4: ...4...
Page 14: ...14...
Page 15: ...15 I MANUALE D USO I...
Page 40: ...40...
Page 41: ...41 GB USER S MANUAL GB...
Page 66: ...66...
Page 67: ...67 D BEDIENUNGSANLEITUNG D...
Page 92: ...92...
Page 93: ...93 F MANUEL D UTILISATEUR F...
Page 118: ...118...
Page 119: ...119 E MANUAL DE USUARIO E...
Page 144: ...144 0MNUMO4NPB...
Page 145: ......
Page 146: ...0MNUMO4NPB...