RENTAL & SILENT ENERGY RENTAL GENSETS 4.3
35
INCIDENT
DESCRIPTION OF ELECTRICAL TRIPS
ALARM
Electrical trip
Generator over current
Generator set current above electrical trip setting.
ALARM
Electrical trip
Auxiliary inputs
Auxiliary inputs can be configured and will display the message as
written by the user
ALARM
Electrical trip
kW overload
The total kW is above electrical trip setting.
ALARM
Electrical trip
Earth fault
The earth fault current is above electrical trip settings (only under
customer request)
ALARM
Electrical trip
Negative phase sequence
Indicates “out of balance” current loading of the generator set.
Note: Electrical trips are latching and stop the generator set but in a controlled manner. Firstly de-energize the “close
generator” output to remove the load from the generator set, and later, cool down and shutdown the unit.
Typical LCD Display Screens
Indicates that the generator set will respond to either a
mains failure or an active remote start.
Indicates that generator set is in automatic mode and has
been initiated after a mains failure has been detected.
Indicates generator set running normally in automatic
mode. Also indicates the average line to neutral voltage (L-
N), the highest of the three phase currents, the rated
frequency, average line-to-line voltage (L-L) and total kilowatts.
Measurement Parameter Display Screens:
Coolant temperature in degrees (ºC) Celsius and
degrees Fahrenheit (ºF)
Displays engine oil pressure in Bar, PSI and kPa.
All three generator line currents.
Summary of Contents for DPR 100
Page 1: ......