RENTAL & SILENT ENERGY RENTAL GENSETS 4.3
20
If you have acquired an MTU engine, on occasions, with the generator set on and the engine
stopped, the engine's central unit will consume a large quantity of the battery's energy, so it is possible
that it runs flat and it is impossible to start it up again. For this reason, there is a selector on the
switchboard that disconnects the battery in the event of an extended stop. For this purpose, we advise you
to carry out the following start-up process:
1) Switch the selector to position 1.
2) Start up the generator set.
3) Switch the selector to position 0.
Note: Step 1 is strongly recommended, as if the selector is in position 0 once the generator set is running, the board will remain
without a power supply.
IT is recommended to avoid keeping the central unit in position 1 for more than 2 days, as the batteries will discharge
completely, which would impede the generator set starting up again later. If the selector is moved to 0 while the generator
set is running, the generator set will not stop. The battery can only be disconnected with the engine stopped.