34
7.4.4. Installer
The installer menu should be accessed only by qualified personnel. Some of the set
points that can be regulated from this menu can have large effects on the unit perfor-
mance depending on the type of commissioning and installation. There should be a
proper match between installer set points and type of installation in order to optimize
the performance and lifetime of the unit.
In order to access the Installer Menu, a 4-digits password needs to be entered. The
password is: 2016. All temperatures are expressed in °C.
Code Set point
name
Description
Range
Factory
setting
D0
Reset all
All the set points are reset to original factory set-
tings. Also the Information menu and the installer
set points are modified.
OFF/ON
OFF
D1
Errors
The alarms of the unit can be checked here.
-
-
D2
D2.0
Address
Modbus address. The Modbus address can be set
between 1 and 247.
1-247
30
D2.1 Baud
Rate
Modbus baud rate. The Modbus baud rate can be set
between 19200 and 9600.
9600/
19200
19200
D2.2 Parity
Modbus parity. The Modbus parity can be set be-
tween Even or Odd or deactivated.
Even/
Odd/
None
Even
D2.3
Write
enable
Modbus modify. If this function is activated, it is
possible to modify the set points kept for develop-
ment with a data logger.
OFF/ON
ON
D3
Fan max
speed
The maximum fan speed (%) can be regulated. This
is the highest limit at which the fan can run both
when the ventilation function is active and when the
heat pump is in standard operation.
0-100
70
(outdoor)
D4
Fan medi-
um speed
The medium fan speed (%) can be adjusted.
0-100
50
(outdoor)
D5
Fan min
speed
The minimum fan speed (%) can be adjusted.
0-100
40
(outdoor)
D6
AUTO
speed
The automatic speed of the fan (%) when the heat
pump is running in AUTO and ECO mode can be
regulated. This is a nominal value while the fan
speed may automatically vary its speed at a higher
level, depending on the operating conditions.
0-100
57
(indoor)/
48
(outdoor)
Modbus