33
7.4.3. General
The general section collects all the standard settings that have little or no effect on
the heat pump operation, exept for the menu item Reset.
Activating the Reset function brings all the set points to the factory settings value.
The set points of the General menu are described in the Table below
Code Set point
name
Description
Range
Factory
setting
B8
Floor T*
The desired floor heating temperature in °C with
hysteresis of 1K.
15 - 40
35
B9
Cooling*
The Cooling function can be activated. See installer
menu D28 (Cooling type).
OFF/ON OFF
B10
Cooling T*
The air temperature set point (°C) below which the
heat pump stops, when the unit is in the Cooling
function.
10 - 30
21
Code
Set point
name
Description
Range
Factory
setting
C0
Reset
The set points in the user menu are reset. The
more advanced settings can be reset only from the
installer menu. The information as number of hours
of the compressor and fan cannot be reset.
OFF/ON
OFF
C1
Info
The software version is displayed.
-
-
C2
Time
The time can be adjusted here.
-
-
C3
Date
The date can be adjusted here.
-
-
C4
Day
The day of the week can be selected.
-
Monday
C5
Language More languages can be selected.
-
English
C6
Contrast
The contrast of the screen can be adjusted.
0-10
5