ENGLISH

6

5.

PROGRAMMING

The board can operate in 4 different modes:

Crepuscular mode
Timed mode with crepuscular control
Timed mode
Bistable mode

5.1

Crepuscular mode

In this mode, the relay which is actually the board output is controlled strictly by the crepuscular sensor.

When incident light on the photo-transistor falls beneath the threshold set with the TR1 trimmer, the LD1 red LED

lights up; 15 seconds after that moment, the output relay is energised; it stays energised for as long as incident light

on the phototransistor does not rise above a threshold set by the TR1 trimmer, but different from the preceding one;

at that moment, the LD1 red LED goes OFF and, after 25 seconds, the relay de-energises; the two thresholds -

lighting up and switching off - are different: the switching off threshold is about double the lighting up threshold, in

terms of luminosity. Light sensitivity and, therefore, the switching off threshold, increase by turning TR1 anti-

clockwise. To ensure that the above relay switchovers occur it is essential that, during the delay time (15 or 20

seconds depending on switching)incident light must not change suddenly and exceed the opposite threshold, i.e.

the LD1 red LED must remain stable.

5.2

Timed mode with crepuscular control

In this mode, the crepuscular sensor supplies clearance for the relay to be energised, if incident light on the FT1

phototransistor falls below the set threshold:  15 seconds after that moment, the board operates in the same way

as in "Timed mode".  Before these 15 seconds elapse, the board does not react to any input received through J1, J2

and J3.  If, after 15 seconds have elapsed from the time when luminosity had exceeded the lighting up threshold,

luminosity rises again, exceeding the switching off threshold, the LD1 red LED goes off: 25 seconds after that

moment, if the relay had been energised, it de-energises and can no longer be energised by means of the outside

commands, until incident light falls once again under the lighting up threshold. In this case too, to ensure that the

status change occurs, the status of the LD1 red LED must remain stable during the delay time count.

5.3

Timed mode

In this mode, the board behaves like a timed switch, and the crepuscular sensor is ignored.  In rest state, the relay

is always de-energised; when a valid energising signal arrives through connectors J1, J2 or J3, the relay energises;

when no energising signal is supplied from outside, the time count begins and, when it has elapsed, the relay de-

energises. If a valid energising signal is received from the outside during the count, the relay remains energised,

and the time count restarts from the beginning when the energising signal from the outside terminates.

5.4

Bistable mode

In this mode, the board behaves like a normal bistable switch; in rest state, the relay can be both energised and

de-energised; any valid  energising signal from the outside causes the relay to switch; the relay switches as soon

as the external signal is recognised as valid, and not when it terminates.

6.

SELECTIONS

The operating mode and lighting duration time of the timed modes can be selected with Dipswitch DS1.  DIPswiches [1-

6] select the delay time as shown in fig.3.  DIPswiches [7 and 8] select the operating modes as shown in fig.3.

1  2 3  4  5  6  7 8

ON

OFF

SW7 SW8 Logic

on on

Crepuscular mode

off on

Timed mode with crepuscular control

on off

Timed mode

off off

Bistable mode

SW1 SW2 SW3 SW4 SW5 SW6

Pause time

off on on on on on

5 sec.

off off on on on on

15 sec.

on off off on on on

30 sec.

on on off off on on

60 sec.

on on on on off on

2 min.

on on on off off on

5 min.

off off off off off on

10 min.

Summary of Contents for JA338

Page 1: ...LOI NORMES D INSTALLATION INSTRUCCIONES PARA EL USO NORMAS DE INSTALACI N BETRIEBSANLEITUNG INSTALLATIONSVORSCHRIFTEN SCHEDAINTERRUTTORECREPUSCOLARE TEMPORIZZATO CREPUSCULAR TIMEDSWITCHBOARD CARTEINTE...

Page 2: ...mechanical parts must conform to the provisions of Standards EN 12604 and EN 12605 For non EU countries to obtain an adequate level of safety the Standards mentioned above must be observed in addition...

Page 3: ...ressi in morsettiera Alimentazione di rete 230Vac Pulsante accessione luci Ingresso per impulso da lampeggiante di centrale di comando Uscite in morsettiera luci esterne 230Vac 1500W max 2 2 Parametri...

Page 4: ...eggere il collegamento con un fusibile da 10A C Fase per lampada esterna Collegare delle luci esterne con potenza max 1500W L Fase lampeggiatore Collegare lafase del lampeggiatore della centrale di co...

Page 5: ...perando la soglia di spegnimento il LED rosso LD1 si spegne dopo 25 secondi a partire da tale istante il rel se era eccitato si diseccita e non pi possibile eccitarlo attraverso comandi esterni fino a...

Page 6: ...puts 230 Vac mains power supply Lighting up push button Input for pulse from control unit flashing lamp Terminal board outputs 230 Vac 1500W max outside lights 2 2 Operating parameters Logic 4 Operati...

Page 7: ...upplying outside lights NB protect the connection with a 10A fuse C Phase for outside lamp Connect outside lights with maximum power of 1500W L Flashing lamp phase Connect the phase of control unit fl...

Page 8: ...rises again exceeding the switching off threshold the LD1 red LED goes off 25 seconds after that moment if the relay had been energised it de energises and can no longer be energised by means of the o...

Page 9: ...ion de r seau 230Vca Poussoir d allumage des lumi res Entr e pour impulsion provenant du clignotant de la centrale de commande Sorties bornier lumi res externes 230Vca 1500W maxi 2 2 Param tres de fon...

Page 10: ...se pour la lampe externe Connecter des lumi res externes avec une puissance maxi de 1500W L Phase du clignotant Connecter la phase du clignotant de la centrale de commande Dans ce cas le clignotant a...

Page 11: ...ence augmenter d passant le seuil d extinction la LED rouge LD1 s teint au bout de 25 secondes partir de cet instant le relais s il tait excit se d sexcite et il n est plus possible de l exciter trave...

Page 12: ...eta de bornes Alimentaci n de red 230Vac Pulsador encendido luces Entrada para impulso de destellador de central de mando Salidas en regleta de bornes luces externas 230Vac 1500W m ximo 2 2 Par metros...

Page 13: ...nexi n con un fusible de 10A C Fase para l mpara externa Conectar luces externas con potencia m xima de 1500W L Fase destellador Conectar la fase del destellador de la central de mando En este caso el...

Page 14: ...luminosidad vuelve a subir superando el umbral de apagado el Diodo rojo LD1 se apaga transcurridos 25 segundos a partir de dicho instante el rel si estaba excitado se desexcita y no se puede excitarl...

Page 15: ...emmenleiste Netzversorgung 230Vac Taste Einschaltung Licht Eingang f r Impuls der Blinkleuchte der Steuerzentrale Ausg nge aus Klemmenleiste Externe Lampen 230 Vac max 1500W 2 2 Betriebsparameter Steu...

Page 16: ...it einer Sicherung mit 10 A gesch tzt werden C Phase f r externe Lampe Die externen Lampen sind mit einer Leistung von maximal 1500W anzuschlie en L Phase Blinkleuchte Die Phase der Blinkleuchte an di...

Page 17: ...Einschaltschwelle berschritten wurde die Intensit t wieder an und berschreitet die Ausschaltungsschwelle schaltet sich auch die rote LED Diode aus nach Ablauf eines Zeitraumes von 25 Sekunden ab diese...

Page 18: ...note notes note notas anmerkung...

Page 19: ...os los telemandos o cualquier HINWEISE F R DEN INSTALLATIONSTECHNIKER ALLGEMEINE SICHERHEITSVORSCHRIFTEN 1 ACHTUNG Um die Sicherheit von Personen zu gew hrleisten sollte die Anleitung aufmerksam befo...

Page 20: ...nicalorcommercialreasons atanytimeand withoutrevisingthepresentpublication Lesdescriptionsetlesillustrationsdupr sentmanuelsontfournies titre indicatif GENIUS se r serve le droit d apporter tout momen...

Reviews: