6.9
OPEN
CLOSE
STOP
CAL
RUN
SCROLL
SCROLL
SET
CLEAR
MAX RUN TMR SET
Figure
15
TO RESET
1) Press CAL/RUN to enter calibration mode.
2) Press SCROLL (up or down) until display reads
”MAX RUN TMR > SET.” Figure 15.
3) Press SET/CLEAR until display reads ”MAX RUN TMR > CLR.”
4) Press CAL/RUN to return to RUN mode.
5) Cycle the door between limits.
NOTE: The Max Run Timer must be reset each and every time the Travel Limits are adjusted.
Resetting the MRT
(The Max Run Timer is set automatically once the unit is cycled between
Limits. The Max Run Timer prevents the unit from running continuously in the event of a problem.
The MRT’s are set to the time required to run from one limit to the other, plus 5 seconds (nominal).
When the MRT is exceeded, the operator stops and will not respond to any command until it is reset
by pressing one of the Calibration keys or by cycling power to the unit.
CAL
RUN
SET
CLEAR
CAL
RUN
SCROLL