Operation Manual for ZBL-R620/R630 Rebar Locator 

Fig. 2.7 Pre-Scanning 

In  order  to  know  the  rebar’s  general  distribution  a 

pre-scan may be performed on the concrete element. It is an 

important part when selecting scan starting point. A pre-scan 

allows  real-time  display  of  test  information  without  saving 

data.   

Generally, the rebars of the top layer are located first, and 

then a measurement of the central point between two top layer 

rebars is needed in order to locate lower layer rebars. 

1) Rebar Location (Fig. 2.7, also see video) 

Put the probe on the surface of the concrete element; 

ensuring that the probe is parallel to the rebar. Be sure to move the probe smoothly and 

evenly in a uniform motion. When the probe moves closer to the rebar, the signal strength 

bar rises, the signal value is larger, and the concrete cover thickness value becomes 

lower; once the peak value has been reached the instrument will produce a “beep” sound, 

and the screen displays related information. The display style differs according to the 

different scan mode. 

o accurately determine the peak of the signal move the probe in the opposite 

direction until the signal value is largest, and the thickness is the lowest. The central line 

of the probe is then the accurate location of the rebar. Select the central location of the 

two rebars which have largest distance between each other as the starting point of 

scanning. (Please mark this point with a pen) 

2)  Rebar Direction (Fig. 2.8, video) 

The direction of rebars can be detected by the 

following two methods. 

  When the rebar location is known, rotating the 

probe directly on the rebar. When the signal 

value is the largest and the thickness value is 

the smallest, the direction of the probe is the 

direction of the rebar. 

  Detect two rebars location along two parallel 

measuring lines, the connected line between the 

two locations is then the direction of the rebar. (See fig. 2.8) 

3) Estimate the rebar diameter   

When the probe is located directly on the rebar, and is parallel to the rebar. 

  Press 

【↑】

key, the screen displays the rebar diameter and the concrete cover 

thickness. 

Note: There is a black triangle symbol before the thickness value; it means the thickness 

does not correspond to the pre-set diameter. 

  In abnormal testing conditions, the rebar diameter may not be measured. 

 

2.6.2 Start Scanning (Save Scanning) 

Put the probe in the scan starting point as determined by the pre-scan, move the 

probe, the test result may vary with the probe location 

1) General Test 

Fig. 2.8 Rebar Distribution 

Test Line 1 

Test Line 2 

Summary of Contents for ZBL-R620

Page 1: ...ZBL R620 630 Rebar Locator Operation Manual...

Page 2: ...2 2 1 System Connection 3 2 2 Startup 4 2 3 System Reset 4 2 4 Choosing Scan Mode 5 2 5 Parameter Settings 5 2 6 Scan Operation 7 2 7 Data Display 10 2 8 Data Transmission 10 2 9 Deleting Data 12 2 1...

Page 3: ...ver and rebar diameter 1 2 Components of ZBL R620 R630 ZBL R620 R630 Rebar Locator is composed of a main instrument body a probe a scan car ZBL R630 only and signal transmission wire The probe has dir...

Page 4: ...erface Soft keyboard interface Fig 1 2 Menu Operation Interface The testing interface is used to scan data and display image including shown in Fig 1 3 General test scan Profile scan ZBL R630 only Gri...

Page 5: ...ig 2 1 Insert the plug black of the signal line into the socket on the left of the rebar locator rotate clockwise and lock it tightly in place Insert the other end of the signal line into the socket o...

Page 6: ...ry must be re charged If the automatic self test is OK it automatically enters the menu display after about five seconds Shortcuts in Main Menu interface key background light on off switch keys move c...

Page 7: ...ess highlight option Back key save current parameter setting return to previous menu and reset the system Menu key return to main menu interface Parameter amendment 1 General situation keys select the...

Page 8: ...and the interface automatically returns to the parameter setting interface 3 Thickness setting Set the concrete cover thickness of test rebar the available range is 10 99mm the initial value is automa...

Page 9: ...odes 1 General Test It is the basic scan mode of R630 It accurately measures the thickness of concrete cover and the diameter of rebar it may also judge if the component conforms to international stan...

Page 10: ...d the thickness is the lowest The central line of the probe is then the accurate location of the rebar Select the central location of the two rebars which have largest distance between each other as t...

Page 11: ...ing point unit cm will be displayed above the black dot The instrument automatically saves the test data and the image Press Back key return to parameter setting interface Press Menu key access the ma...

Page 12: ...ce move the cursor to data display option Press Enter to access the components list interface 2 In data display interface The left column shows the components list listed in descending order with the...

Page 13: ...ot recognized and the computer indicates that it has found new hardware device the user is directed to the appendix of R650 software operation manual for further advice 2 Computer operation Launch Reb...

Page 14: ...plays deleting 2 10 System Settings When accessing the system setting function the information below may be amended Fig 2 16 Date Year Month Day Time Hour Minute Second 24hours mode Power status may b...

Page 15: ...s signal cable is correct Check if the power is low battery power 0 3 3 No keypad tone Check system settings turn keyboard tones on then save settings If settings are normal but there are still no key...

Page 16: ...ndix A General Principles of Rebar Testing Scan surface should be smooth and flat If the surface is too rough to clean put a thin board on the scan surface after completing the scan the board s thickn...

Reviews: