MS3002 Manual v.200909
Page 14
3. If the tool suddenly stalls while
cutting wood, release the trigger
switch, unplug the tool, and free the
blade from the wood. The saw may
now be started and the cut finished.
4. FUSES
may “blow” or circuit
breakers may trip frequently if:
a. MOTOR
is overloaded –
overloading can occur if you
feed too rapidly or make too
many start/stops in a short time.
b. LINE VOLTAGE
is more
than 10% above or below the
nameplate voltage rating. For
heavy loads, the voltage at
motor terminals must equal
the voltage specified on the
nameplate.
c. IMPROPER
or dull saw blades
are used.
5. Most motor troubles may be traced
to loose or incorrect connections,
overload, low voltage or inadequate
power supply wiring. Always check
the connections, the load and supply
circuit if the motor doesn’t run well.
Check minimum gauge for the length
of cord you are using on the chart
below.
GUIDELINES FOR
EXTENSION CORDS
Use a proper extension cord. Make sure
your extension cord is in good condition.
When using an extension cord, be
sure to use one heavy enough to carry
the current your product will draw. An
undersized cord will cause a drop in
line voltage, resulting in loss of power
and cause overheating. The table below
shows the correct size to use depending
on cord length and nameplate ampere
rating. If in doubt, use the next heavier
gauge. The smaller the gauge number,
the heavier the cord.
Be sure your extension cord is
properly wired
and in good condition.
Always replace a damaged extension
cord or have it repaired by a qualified
person before using it. Protect your
extension cords from sharp objects,
excessive heat and damp or wet areas.
Use a separate electrical circuit for
your tools.
This circuit must not be less
than a #18 wire with a 9 A time lag fuse.
NOTE: When using an extension cord on
a circuit with a #18 wire, the extension
cord must not exceed 25 feet in length.
Before connecting the tool to the power
line, make sure the switch is in the OFF
position and the electric current is rated
the same as the current stamped on the
motor nameplate, running at a lower
voltage will damage the motor.
In all cases make certain the
receptacle in question is properly
grounded. If you are not sure, have
a certified electrician check the
receptacle.
MINIMUM GAUGE FOR EXTENSION CORDS (AWG)
(When using 120 volts only)
Ampere Rating
Total length of Cord
More Than Not More Than 25ft. 50ft. 100ft. 150ft.
0 6
18 16 16 14
6 10
18 16 14 12
10 12
16 16 14 12
12 16
14 12 Not Recommended
ELECTRICAL REQUIREMENTS AND SAFETY