![Generac Power Systems PWRcell X11402 Installation And Owner'S Manual Download Page 44](http://html.mh-extra.com/html/generac-power-systems/pwrcell-x11402/pwrcell-x11402_installation-and-owners-manual_2209245044.webp)
Commissioning
40
Installation and Owner’s Manual for Generac PWRCell Inverter
5.
From the Inverter menu select “PWRcell Configu
-
ration.”
6.
See
.
Uncheck Priority Backup from
the “Enabled SysModes” list.
7.
Find the Zero Import setting and select
“ENABLED”.
8.
Click the “Submit” button at the bottom of the page.
9.
Be sure to generate a compliance report once all
compliance settings have been set. See
Figure 6-30. Zero Import
Export Limit
(CRD200 Import Only compliance): allows a qualified
installer to restrict the export to a connected utility grid
and set an Export Limit value. When the Export Limit
value is set to 0, this setting functions as a “Zero Export”
mode or CRD200 Import Only mode. For this setting's
value to be active, the setting Export Limiting must be
ENABLED.
NOTE:
Export Limiting is one-time settable. Once set,
some utilities may require the request to unset this set
-
ting to come from the utility. To unset Export Limiting,
please contact Generac PWRcell Technical Support.
NOTE:
Export Limit setting can only be decreased from
its current value. To reset the value of this setting, please
contact PWRcell Technical Support.
How to set:
1.
Navigate to the inverter device page.
2.
Disable inverter if enabled.
3.
Access the Installer Configuration Tool through the
REbus Beacon. See
4.
Once logged onto the Installer Configuration Tool,
select “Inverter.”
5.
From the Inverter menu select “PWRcell Configu
-
ration.”
6.
See
. Find the Export Limiting setting
and select “ENABLED”.
7.
Scroll to the bottom and locate Export Limit.
8.
Change the setting value. If Zero Export is neces
-
sary, make this value 0 (watts).
9.
Click the “Submit” button at the bottom of the page.
10.
Be sure to generate a compliance report once all
compliance settings have been set. See
section for more information.
Figure 6-31. Export Limit
NOTE:
These settings are included in the Compliance
PDF. See
section for more infor
-
mation.
011685
011686
Summary of Contents for PWRcell X11402
Page 63: ......