Location and Compliance
12
Installation and Owner’s Manual for Generac PWRcell Inverter
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single point of com
-
mon coupling.
All PWRcell Inverters are shipped from the factory in compliance with all UL 1741 requirements, including IEEE 1547.
If permission to operate (PTO) is dependent on compliance to a specific utility standard, follow the steps covered in the
Set Inverter Grid Compliance (optional)
section in this manual.
Voltage Trip Thresholds
See
for the default fixed voltage trip setpoints. All over voltage and under voltage trip conditions result in a
300-second restart delay time after the trip threshold has been exceeded for the listed number of cycles.
The inverter is disconnected from the grid during this 300-second delay.
Frequency Trip Thresholds
See
for the default fixed frequency trip setpoints. All over frequency and under frequency trip conditions
result in a 300-second restart delay time after the trip threshold has been exceeded for the listed number of cycles.
The inverter is disconnected from the grid during this 300-second delay.
*Value of 999 indicates a disabled threshold for voltage trips.
**Value of zero indicates a disabled threshold for frequency trips.
Table 3-3. Voltage Trip and Frequency Thresholds
Voltage Trip Thresholds
Frequency Trip Thresholds
Threshold
Threshold
(% of nominal)
No. of Cycles
Threshold
Threshold
(% of nominal)
No. of Cycles
OV4
999*
1
OF4
0**
1
OV3
130
1
OF3
0**
1
OV2
120
10
OF2
0**
1
OV1
110
60
OF1
0.5
10
UV1
88
120
UF1
0.7
10
UV2
50
10
UF2
0**
1
UV3
999*
1
UF3
0**
1
UV4
999*
1
UF4
0**
1